TOPFLEX®-EMV-UV-2XSLCYK-J for power supply connections to frequency converters, double screened, higher current carrying capacity, 0,6/1kV, meter marking
Special motor power supply cable for frequency converters adapted to DIN VDE 0250
Temperature range flexing -5°C to +90°C fixed installation -40°C to +90°C
Permissible operating temperature at conductor +90°C
Nominal voltage U0/U 600/1000 V
Max. operating voltage A.C. and 3-phase 700/1200 V DC operation 900/1800 V
Test voltage 4000 V
Insulation resistance min. 200 MOhm x km
Coupling resistance acc. to different cross-sections max. 250 Ohm/km
Minimum bending radius free-movement for outer Ø: up to 12 mm: 10x cable Ø > 12-20 mm: 15x cable Ø > 20 mm: 20x cable Ø fixed installation for outer Ø: up to 12 mm: 5x cable Ø > 12-20 mm: 7,5x cable Ø > 20 mm: 10x cable Ø
Radiation-resistance up to 80x106 cJ/kg (up to 80 Mrad)
Cable structure
Bare copper-conductor, to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
Core insulation of cross-linked polyethylene (XLPE)
Core identification BN, BK, GY
GN-YE conductor
Cores stranded in concentric layers
1. Screen with special aluminium film 2. Tinned copper braided screen, approx. 85% coverage
Outer sheath of special PVC
Sheath colour black (RAL 9005)
with meter marking
Properties
Low mutual capacitance
Low coupling resistance for high electromagnetic compatibility
UV-resitant
Outdoor application, possible for installation in underground at 4G16 mm²
This screened motor supply cable with low mutual capacitance of the single cores because of the special XLPE core insulation and low screen capacitance enable a low-loss transmission of the power compared to PE-sheathed connecting cables
Due to the optimal screening an interference-free operation of frequency converters is obtained
The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers
Tests
self-extinguishing and flame retardant acc. to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B)
Meets EMC requirements acc. to EN 55011 and DIN VDE 0875 part 11
Note
**) The current carrying capacity for permanent operation at ambient temperature of 30°C. For deviating ambient temperatures the conversion factors should be used and for further see the indication in DIN VDE 0298 part 4.
AWG sizes are approximate equivalent values. The actual cross-section is in mm².
Application
This TOPFLEX®-EMV-UV-2XSLCYK-J motor power supply cable for the frequency converters assures electromagnetic compatibillity in plants and buildings, facilities with units and operating equipment where the fields of electromagnetic interference might cause adverse effects on the surroundings. Respecting the permissible operating temperature at the conductor of +90 °C permits a higher current carrying capacity than PE insulated power distribution cables. As a supply and connecting cable for medium mechanical stresses in fixed installations and forced movements in dry, moist and wet environments and for outdoor applications, possible for installation in underground at 4G16 mm². Used in the automotive and food industries, environmental technology, packaging industry, machine tools. Handling equipment, for SIMOVERT drives, they are particularly suitable for use with industrial pumps, ventilators, conveyor belts and air-conditioning installations and similar applications. Installation in hazardous areas. EMC = Electromagnetic compatibillity The screen must be connected at both ends and ensure large-area contact over the entire cable circumference for compliance with the functional interference requirements of EN 55011. CE = The product is conformed with the EC Low-Voltage Directive 2006/95/EC.