    A-XLPE/Aluminum interlocked armor/PVC Armored Cable 90°C, 600 V 多芯波浪狀鋁管鎧裝控制電纜
    看原圖
    5258946




    商品編號: A-7A-1402A

    A-XLPE/Aluminum interlocked armor/PVC Armored Cable 90°C, 600 V 多芯波浪狀鋁管鎧裝控制電纜


    For use in control circuits in industrial plants,commercial buildings, and central and sub-stationutility applications. May be installed in trays, racks,hangers, etc., eliminating the need for conduit.Suitable for indoor and outdoor installation.



    ★★★★商品說明★★★★

    Armored Cable
    Interlocked Armor

    600 V Multiconductor

    Aluminum interlocked armor
    XLP insulation
    90°C, 600 V


    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, bare, annealed copper per ASTM B3 and B8
    2. INSULATION: Cross-Linked Polyethylene (XLP) Type XHHW-2. Color coding is Method 1,
    Table E-2 (formerly K-2)
    3. ASSEMBLY: The insulated conductors and a single uninsulated, bare copper ground wire are cabled with fillers to make round
    4. ARMOR: Aluminum interlocked armor
    5. OVERALL JACKET:Black, sunlight-resistant Polyvinyl Chloride (PVC)
    6. STANDARDS:Cables meet the UL 1685 and IEEE 1202 70,000 Btu/hr vertical tray flame tests and are marked "for CT use". Individual conductors listed Type XHHW-2 per
    UL 44 and cable is listed Type MC per UL 1569 requirements
    7. AMPACITY: Based on not more than three conductors in raceway or cable or earth based on an ambient temperature of 30°C per 2008 NEC table 310.16. All multiconductor
    values have been derated per 2008 NEC Table 310.15(B)(2)(a)
    8. TEMPERATURE:90°C
    9. VOLTAGE: 600 V


    APPLICATIONS
    For use in control circuits in industrial plants, commercial buildings, and central and substation utility applications. May be installed in trays, racks, hangers, etc.,
    eliminating the need for conduit. Suitable for indoor and outdoor installation.