    A-EPR/Aluminum interlocked armor/PVC 2,400 V 90°C Three Conductor Nonshielded Armored Cable  EPR/PVC 3芯耐高壓波浪狀鋁管鎧裝控制電纜
    看原圖
    5258960




    商品編號: A-7B-0603A

    A-EPR/Aluminum interlocked armor/PVC 2,400 V 90°C Three Conductor Nonshielded Armored Cable EPR/PVC 3芯耐高壓波浪狀鋁管鎧裝控制電纜


    For use in power circuits in industrial plants,commercial buildings, and central and sub-stationutility applications. May be installed in trays, racks,hangers, etc., eliminating the need for conduit.Suitable for indoor and outdoor installation.



    ★★★★商品說明★★★★

    Armored Cable
    Interlocked Armor

    2,400 V Three Conductor Nonshielded

    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, bare, annealed copper per ASTM B3, strand shield is an extruded
    semiconducting material
    2. INSULATION: Ethylene Propylene Rubber (EPR), insulated phase conductors are numbered
    3. ASSEMBLY: The three-phase conductors are cabled with a Class B stranded, uninsulated ground wire and fillers to make round, a binder tape is applied overall
    4. ARMOR: Aluminum interlocked armor
    5. OVERALL JACKET:Yellow, extruded, sunlight-resistant Polyvinyl Chloride (PVC)
    6. STANDARDS:UL Listed Type MV-90 per UL 1072 and Type MC per UL 1569, cable meets requirements of ICEA S-96-659 (NEMA WC 71). Cables are listed "for CT use" and meet
    the IEEE1202 (70,000 Btu/hr) and ICEA T-29-520 (210,000 Btu/hr) flame tests
    7. AMPACITY: Based on a three-conductor cable isolated in air with a conductor temperature of 90°C and an ambient temperature of 40°C per 2008 NEC table 310.71
    8. TEMPERATURE: 90°C
    9. VOLTAGE:2,400 V
     

    APPLICATIONS
    For use in power circuits in industrial plants, commercial buildings, and central and substation utility applications. May be installed in trays, racks, hangers, etc.,
    eliminating the need for conduit. Suitable for indoor and outdoor installation.