    A-EPR/Aluminum interlocked armor/PVC 15KV 105°C Three Conductor 133% Insulation Level Armored Cable  EPR/PVC 3芯耐高壓波浪狀鋁管鎧裝控制電纜
    看原圖
    5258974




    商品編號: A-7D-0203A

    A-EPR/Aluminum interlocked armor/PVC 15KV 105°C Three Conductor 133% Insulation Level Armored Cable EPR/PVC 3芯耐高壓波浪狀鋁管鎧裝控制電纜


    For use in power circuits in industrial plants, commercial buildings, and central and substation utility applications. May be installed in trays, racks, hangers, etc.,
    eliminating the need for conduit. Suitable for indoor and outdoor installation.




    ★★★★商品說明★★★★

    Armored Cable
    Interlocked Armor

    15 kV Three Conductor 133% Insulation Level

    Aluminum interlocked armor
    EPR insulation


    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, bare, annealed copper per ASTM B3 and B8, strand shield is an
    extruded semiconducting material
    2. INSULATION: Ethylene Propylene Rubber (EPR)
    3. SHIELDING: An extruded semiconducting thermoset insulation shield is applied over the insulation and then an uncoated copper tape is helically applied. The method of phase
    identification will be similar to ICEA Method 3 (1-Black, 2-Red, 3-Blue)
    4. ASSEMBLY:The three-phase conductors are cabled with a Class B stranded, uninsulated ground wire and fillers to make round, a binder tape is applied overall
    5. ARMOR: Aluminum interlocked armor
    6. OVERALL JACKET: An extruded covering of red Polyvinyl Chloride (PVC) is applied overall that meets UL sunlight-resistance requirements
    7. STANDARDS: Listed Type MV-105 per UL 1072 and Type MC per UL 1569 and is marked for CT use. Cable meets requirements of ICEA S-93-639 (NEMA WC74) and AEIC CS8.
    Cable passes UL 1685 and IEEE1202/FT4 (70,000 Btu/hr) and ICEA T-29-520 (210,000 Btu/hr) flame tests.
    8. AMPACITY: Based on a 5 kV-35 kV three-conductor cable isolated in air with a conductor temperature rating of 105°C and an ambient temperature of 40°C per
    2008 NEC table 310.71
    9. TEMPERATURE:105°C
    10.VOLTAGE: 15 kV


    APPLICATIONS
    For use in power circuits in industrial plants, commercial buildings, and central and substation utility applications. May be installed in trays, racks, hangers, etc.,
    eliminating the need for conduit. Suitable for indoor and outdoor installation.