| | 600V MULTI CONDUCTOR Aluminum Armor XLP Insulation Inner and Outer PVC Jackets 90°C, UL & CSA 600V APPLICATIONS: For use in control circuits in industrial plants,commercial buildings, and central and substation utility applications. May be installed intrays, racks, hangers, etc., eliminating the need for conduit. Suitable for indoor and outdoor installation.
SPECIFICATIONS: 1. CONDUCTOR: Class B stranded, bare, annealed copper per ASTM B-3, B-8. 2. INSULATION: Cross-linked polyethylene (XLP) per ICEA S-73-532 (NEMA WC57), Type XHHW-2 requirements of UL and RW90 requirements of CSA. Color coding is Method 1, Table E-2 (formerly K-2) (2 & 3 conductors) or Method 4 (4 or more conductors). 3. ASSEMBLY: The insulated conductors are cabled with a single UL, uninsulated ground wire and fillers to make round. 4. INNER JACKET: Black, sunlight resistant polyvinyl chloride (PVC) applied per ICEA. Jacket is low acid gas per CSA C22.2 No. 0.3. 5. ARMOR: An aluminum interlocked armor is applied overall in accordance with UL 1569, ICEA and CSA. 6. OVERALL JACKET: Black, sunlight resistant polyvinyl chloride (PVC) applied overall per ICEA. Jacket is low acid gas per CSA C22.2 No. 0.3. 7. STANDARDS: Cables meet UL, IEEE 383 and FT-4 70,000 BTU flame tests, and are marked “FOR CT USE.’’ Also meets ICEA T-29-520 210,000 BTU flame test. Meets CSA –40°C cold impact and bend. Individual conductors and completed cables are tested in accordance with UL requirements for Type MC cables and CSA requirements for Type TECK cables. 8. AMPACITY: Based on not more than three conductors in raceway or cable or earth and an ambient temperature of 30°C per NEC 310-16. Values have been derated for more than three conductors in accordance with the NEC. 9. TEMPERATURE: 90°C 10. VOLTAGE: UL & CSA 600 Volts |
| |
|
|