| | Armored Cable Continuous Corrugated Weld 600 V Control Continuous aluminum armor XLP insulation SPECIFICATIONS 1. CONDUCTOR: Class B stranded, bare, annealed copper per ASTM B-3 and B-8 2. INSULATION:Cross-Linked Polyethylene (XLP) meeting the requirements of ICEA S-95-658 (NEMA WC70) and Type XHHW requirements of UL, color coding is Method 1, Table E-2 3. ASSEMBLY:The insulated conductors and a single, uninsulated UL ground wire(s) are cabled with fillers to make round 4. ARMOR: An impervious, corrugated continuous seam-welded aluminum alloy sheath in accordance with UL 1569. Armor is pressure-tested and meets the grounding requirements of NEC Article 250 5. OVERALL JACKET: Black, sunlight-resistant Polyvinyl Chloride (PVC) 6. STANDARDS: Cables are UL Listed for cable tray use and meet the IEEE 1202 (70,000 Btu/hr) flame test. Individual conductors and completed cables are tested in accordance with UL 2225 requirements for Type MC-HL cables 7. AMPACITY: Based on not more than three conductors in raceway or cable or earth and an ambient temperature of 30°C per NEC table 310.16. All multiconductor values have been derated per 2008 NEC Table 310.15(B)(2)(a) 8. TEMPERATURE:90°C 9. VOLTAGE: 600 V
APPLICATIONS Control and lighting circuits in manufacturing and processing plants, feeders in industrial and commercial distribution systems. May be directly buried or installed in cable tray or raceway. |
| |
|
|