| 商品編號: A-7R-0803
A-XLP/Continuous Aluminum Armor/PVC UL 90°C, 600V 3C (CCW) Armored Cable 3芯波紋鋁管鎧裝控制電纜
Primary power and lighting circuits in manufacturing and processing plants, feeders in industrial and commercial distribution systems. May be directly buried or installed in cable tray or raceway. Can be used in Classes I, II and III, Division 1 and 2, hazardous locations covered under NEC Articles 501, 502 and 503. |
| |
| | |
玉山 / 台新 / 華南 / 萬泰 / 兆豐 / 遠東 / 新光 / 永豐 / 第一 / 彰化 / 合庫 / 日盛 / 匯豐 / 渣打國泰世華 / 台北富邦 / 大眾銀行 / 台灣中小企銀/台中商銀 / 澳盛銀行
| |
| | |
| | Armored Cable Continuous Corrugated Weld 600 V Three Conductor Power Continuous aluminum armor XLP insulation SPECIFICATIONS 1. CONDUCTOR:Class B stranded, bare, annealed copper per ASTM B3 and B8 2. INSULATION:Cross-Linked Polyethylene (XLP) meeting the requirements of ICEA S-95-658 (NEMA WC70) and Type XHHW requirements of UL 44. Conductors are identified per ICEA S-58-679, using Method 3, Table 2 for sizes AWG 4 and larger, and using Method 1, Table 2 for sizes AWG 6 and smaller 3. ASSEMBLY:The conductors and ground wires are cabled with fillers to make round 4. ARMOR: An impervious, corrugated continuous seam-welded aluminum alloy sheath in accordance with UL 1569. Armor is pressure-tested and meets the grounding requirements of NEC Article 250 5. OVERALL JACKET:Black, sunlight-resistant Polyvinyl Chloride (PVC) 6. STANDARDS:Cables are marked "for CT use" and pass the UL 1685, IEEE 1202/CSA FT4 70,000 Btu/hr and the ICEA T-29-520 210,000 Btu/hr flame test. Individual conductors are UL Listed Type XHHW per UL 44 and completed cables are UL Listed Type MC-HL UL 2225 per UL 2225 7. AMPACITY: Not more than three conductors in raceway or cable or earth based on an ambient temperature of 30°C per Article 310.16 of the 2008 NEC 8. TEMPERATURE: 90°C 9. VOLTAGE:600 V
APPLICATIONS Primary power and lighting circuits in manufacturing and processing plants, feeders in industrial and commercial distribution systems. May be directly buried or installed in cable tray or raceway. Can be used in Classes I, II and III, Division 1 and 2, hazardous locations covered under NEC Articles 501, 502 and 503. |
| |
|
|