    A-EPR/Aluminum Armor/PVC UL 105°C, 5KV 3C Shielded (CCW) Armored Cable波紋鋁管鎧裝耐高壓3芯電力控制電纜
    看原圖
    5260291




    商品編號: A-7SS-0403

    A-EPR/Aluminum Armor/PVC UL 105°C, 5KV 3C Shielded (CCW) Armored Cable波紋鋁管鎧裝耐高壓3芯電力控制電纜


    Primary power and lighting circuits in manufacturing and processing plants, feeders in industrial and commercial distribution systems, power supply to station auxiliaries in
    electric power stations and substations. May be used in wet or dry locations installed in open tray, trough or ladder.




    ★★★★商品說明★★★★

    Armored Cable
    Continuous Corrugated Weld

    5 kV Three Conductor Shielded

    Continuous aluminum armor
    EPR insulation
    100% and 133% insulation level


    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, bare, annealed copper per ASTM B3 and B8, strand shield is an
    extruded semiconducting material
    2. INSULATION:Ethylene Propylene Rubber (EPR) per ICEA S-93-639 (NEMA WC74), the insulated phase conductors are printed with the numbers "1, "2 and "3
    3. SHIELD: An extruded semiconducting insulation shield is applied per ICEA S-93-639 and an uncoated copper tape shield is helically applied over the insulation shield
    4. ASSEMBLY:The three-phase conductors are cabled with a UL size, Class B stranded, uninsulated ground wire and fillers to make round, a binder tape is applied overall
    5. ARMOR: An impervious, corrugated continuous seam-welded aluminum alloy sheath in accordance with UL 1569, armor is pressure tested and meets the grounding
    requirements of NEC Article 250
    6. OVERALL JACKET: Yellow, sunlight-resistant Polyvinyl Chloride (PVC)
    7. STANDARDS: Cable shall be tested in accordance with UL 1072 requirements for Type MV-105, UL 2225 requirements for Type MC-HL and ICEA S-93-639 (NEMA WC74). The
    cables meet the UL 1685 and IEEE 1202/FT4 (70,000 Btu/hr) and the ICEA T-29-520 (210,000 Btu/hr) vertical tray flame tests and are marked "for CT use". Cables meet the
    qualification testing requirements of AEIC CS-8
    8. AMPACITY: Based on a three-conductor cable isolated in air with a conductor temperature of 90°C and an ambient temperature of 40°C per 2008 NEC table 310.71
    9. TEMPERATURE: 105°C
    10.VOLTAGE:5 kV


    APPLICATIONS
    Primary power and lighting circuits in manufacturing and processing plants, feeders in industrial and commercial distribution systems, power supply to station auxiliaries in
    electric power stations and substations. May be used in wet or dry locations installed in open tray, trough or ladder