    A-EPR/Aluminum interlocked armor/PVC 2,400 V 90°C Three Conductor Nonshielded Armored Cable  EPR/PVC 3芯耐高壓波浪狀鋁管鎧裝控制電纜
    看原圖
    5642165




    商品編號: A-7S-0403

    A-EPR/Aluminum interlocked armor/PVC 2,400 V 90°C Three Conductor Nonshielded Armored Cable EPR/PVC 3芯耐高壓波浪狀鋁管鎧裝控制電纜


    Primary power and lighting circuits in manufacturing and processing plants, feeders in industrial and commercial distribution systems, power supply to station auxiliaries in
    electric power stations and substations. May be used in wet or dry locations installed in open tray, trough or ladder.




    ★★★★商品說明★★★★

    Armored Cable
    Continuous Corrugated Weld

    2,400 V Three Conductor Nonshielded

    Continuous aluminum armor
    EPR insulation
    100% insulation level


    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, bare, annealed copper per ASTM B3 and B8, strand shield is an
    extruded semiconducting material
    2. INSULATION: Ethylene Propylene Rubber (EPR), the insulated phase conductors are printed with the numbers "1, "2 and "3
    3. ASSEMBLY: The three-phase conductors are cabled with UL sized uninsulated ground wires and fillers to make round with a cable tape applied over the core
    4. ARMOR: An impervious, corrugated continuous seam-welded aluminum alloy sheath in accordance with UL 1569. Armor is pressure tested and meets the grounding
    requirements of NEC Article 250
    5. OVERALL JACKET: Yellow, sunlight-resistant Polyvinyl Chloride (PVC)
    6. STANDARDS: Cable are UL Listed Type MV-90 and Type MC-HL and meet ICEA S-96-659 (NEMA WC71) requirements. Cables pass the UL 1685, IEEE 1202 and
    CSA FT-4 (70,000 Btu/hr) and ICEA T-29-520 (210,000 Btu/hr) flame tests and and are marked "for CT use"
    7. AMPACITY:Based on a three-conductor cable isolated in air with a conductor temperature of 90°C and an ambient temperature of 40°C per 2008 NEC table 310.71
    8. TEMPERATURE: 90°C
    9. VOLTAGE:2,400 V


    APPLICATIONS
    Primary power and lighting circuits in manufacturing and processing plants, feeders in industrial and commercial distribution systems, power supply to station auxiliaries in
    electric power stations and substations. May be used in wet or dry locations installed in open tray, trough or ladder.