PART NUMBER:75906
DESCRIPTION:18/6 STRANDED SHIELDED CL3P/CMP/FPLP FT6 PLENUM CABLE
CONSTRUCTION:This cable consists of six bare copper insulated conductors, cabled with an overall shield &drain wire, and an overall jacket.
APPROVALS:UL Standard 13 and 444, NEC Articles 725 and 800.
Power Limited Circuit Cable And Communications Cable Used in Plenum Applications
Construction Parameters:
Conductor 18 AWG Bare Copper
Stranding 7/.0152"
Insulation Material Low Smoke PVC
Insulation Thickness 0.008 Nom.
Insulated Conductor Diameter 0.062 Nom.
Number of Conductors 6
Lay Length 5.00 Nom.
Shield Alum/Mylar
Drain 24 AWG 7/24 Tinned Copper
Jacket Material Low Smoke PVC
Jacket Thickness 0.017 Nom.
Overall Cable Diameter 0.224 Nom.
Approximate Cable Weight 48.7 Lbs/1M Nom.
Flame Rating NFPA 262 Steiner Tunnel Smoke and Flame Test
Electrical & Enviromental Properties:
Temperature Rating -to Operating Voltage 300 V RMS Max.
Capacitance Between Conductors @ 1 KHz 56 pF/ft Nom.
Capacitance Between Conductors to Shield @ 1 KHz 103 pF/ft Nom.
DC Resistance per Conductor @ 20OC 6.29 Ohms/1M Nom.
Insulation Colors Black Red White Green Brown Blue
Jacket Color Beige (Other colors available for minimum order)