PART NUMBERPART NUMBER: 85604
DESCRIPTION: 16/4 SOLID FPLP FT6 CABLE
CONSTRUCTION: This cable consists of two bare copper insulated conductors and an overall jacket.
APPROVALS: UL Standard 1424 and 444, NEC Article 760 and 800
APPLICATION: Fire Alarm Power Limited Circuit Cable Used in Plenum Applications
Construction Parameters:
Conductor: 16 AWG Bare Copper
Stranding: Solid
Insulation Material:Low Smoke PVC
Insulation Thickness: 0.010 Nom.
Insulated Conductor Diameter: 0.071 Nom.
Number of Conductors: 4
Lay Length: 4.00" Nom.
Shield: Alum/Mylar
Drain: 24 AWG Solid Tinned Copper
Jacket Material: Low Smoke PVC
Jacket Thickness: 0.017 Nom.
Overall Cable Diameter: 0.215 Nom.
Approximate Cable Weight: 52.6 Lbs/1M Nom.
Flame Rating: NFPA 262 Steiner Tunnel Smoke and Flame Test
Electrical Properties:
Temperature Rating: -20度to 75度
Operating Voltage: 300V RMS Max
Capacitance Between Conductors@1KHz: 59Pf/ft Nom.
Capacitance Between Conductors to shield@1KHz: 109 pf/ft Nom.
DC Resistance per Conductor@20度: 4.02 Ohms/1M*Nom.
Insulation Colors: Black Red Green Yellow
Jacket Colors: Red (other colors available for min order)
Legend (Surface Ink Print): COLEMAN CABLE 85604 16 AWG 4/C C(ETL)US-TYPE FPLP 75C
-TYPE CMP FT6