    CALEDONIAN-Fire resistant RG11 A/U Coaxial cables MIL-C-17 耐火級低煙無毒 RG-11 A/U 同軸電纜線
    看原圖
    5544250




    商品編號: CALEDONIAN-FR-RG11

    CALEDONIAN-Fire resistant RG11 A/U Coaxial cables MIL-C-17 耐火級低煙無毒 RG-11 A/U 同軸電纜線


    Conductors: Copper clad steel, solid according to IEC(EN) 60228 class 1.
    Insulation: Foamed PE wrapped with fire resistant silicone rubber compound type EI2 as per BS 7655-1.1 or fluoropolymer(FEP) compound.
    Binder: Glass tape
    Overall Screen:
    Screen1: Al-maylar Tape ≥25%
    Screen2: Aluminium Braid
    Screen3: Al-maylar Tape ≥25%
    Screen4: Aluminium Braid
    Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)




    ★★★★商品說明★★★★

    PRODUCTS

    Fire Resistant Coaxial Cables
    RG11 A/U FR
    APPLICATION
    The cables are designed for CCTV, security, smoke detection and evacuation monitoring applications, where continued functionality is required during a fire situation. Due to the zero halogen low smoke construction, this cable is ideal for use in public, commercial and industrial environments.
    Standards
    Basic design to MIL-C-17
    FIRE PERFORMANCE

    Circuit Integrity

    IEC 60331-23; BS 6387 CWZ; DIN VDE 0472-814(FE180);

    CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);

    NF C32-070-2.3(CR1)

    System circuit integrity

    DIN 4102-12, E30 depending on lay system

    Flame Retardance (Single Vertical Wire Test)

    EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

    CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

    Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

    EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

    Halogen Free

    IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

    CEI 20-37/2-1 ; BS 6425-1*

    No Corrosive Gas Emission

    IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

    CEI 20-37/2-2 ; BS 6425-2*

    Minimum Smoke Emission

    IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

    CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

    No Toxic gases

    NES 02-713; NF C 20-454

    Note: Asterisk * denotes superseded standard.
    CABLE CONSTRUCTION
    Conductors: Tinned copper copper wire, stranded according to IEC(EN) 60228 class 2.
    Insulation: Low density PE wrapped with fire resistant silicone rubber compound type EI2 as per BS 7655-1.1 or fluoropolymer(FEP) compound.
    Binder: Glass tape
    Overall Screen: Plain copper wire braid
    Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655:section 2.6 can be offered.)
    Physical AND THERMAL PROPERTIES
    Temperature range during operation (fixed state): -30°C - +70°C
    Temperature range during installation (mobile state): -5ºC - +60ºC
    Minimum bending radius: 8 x Overall Diameter
    Electrical Properties

    Impedance

    75±5Ω

    Capacitance

    67 nF/km

    Velocity ratio(%)

    66

    Insulation resistance

    >2000 Mohm.Km

    Shield coverage

    97%

    DC resistance

     

    Inner conductor

    20.5 Ω/km

    Outer conductor

    4.5 Ω/km

    Attenuation

    Frequency(MHz)

    Attenuation (dB/100 m)

    Attenuation (dB/100ft)

    504.21.28
    1006.21.89
    2009.32.84
    40013.84.21
    50015.54.73
    60017.15.21
    86020.16.13
    100023.47.13

    Return Loss

    Frequency(MHz)

    Return Loss (dB)

    30-300 MHz

    >30dB

    300-600 MHz

    >27dB

    600-900 MHz

    >25dB