    首頁 > > Caledonian-Fire Resistant Power & Control Cables (950°C 180 minutes) 耐火級低煙無毒電力控制電纜線

    CALEDONIAN-FFX100 Fire Resistant Mica+LSZH Insulated Power Cables (Single Core) 雲母耐火級低煙無毒電纜線
    看原圖
    5542861




    商品編號: CALEDONIAN-FFX100

    CALEDONIAN-FFX100 Fire Resistant Mica+LSZH Insulated Power Cables (Single Core) 雲母耐火級低煙無毒電纜線


    450/750V & 600/1000V Mica+LSZH Insulated Power Cables (Single Core)

     FFX100 07mZ1-R (CU/MGT+LSZH 450/750V Class 2)

    FFX100 1mZ1-R (CU/MGT+LSZH 600/1000V Class 2)

    APPLICATION

    This cable is used in fire extinguishing systems, sprinklers, control panels, and exit lights in high-rise buildings, hotels, hospitals, sub-ways, and public facilities.

    Basic design to BS 7211




    ★★★★商品說明★★★★

    Fire Resistant Power & Control Cables
    450/750V & 600/1000V Mica+LSZH Insulated Power Cables (Single Core)
    FFX100 07mZ1-R (CU/MGT+LSZH 450/750V Class 2)
    FFX100 1mZ1-R (CU/MGT+LSZH 600/1000V Class 2)
    APPLICATION
    This cable is used in fire extinguishing systems, sprinklers, control panels, and exit lights in high-rise buildings, hotels, hospitals, sub-ways, and public facilities.
    STANDARDS
    Basic design to BS 7211
    FIRE PERFORMANCE

    Circuit Integrity

    IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);

    CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);

    NF C32-070-2.3(CR1)

    System circuit integrity

    DIN 4102-12, E30 depending on lay system

    Flame Retardance (Single Vertical Wire Test)

    EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;

    VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

    CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

    Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

    EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

    Halogen Free

    IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

    CEI 20-37/2-1 ; BS 6425-1*

    No Corrosive Gas Emission

    IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

    CEI 20-37/2-2 ; BS 6425-2*

    Minimum Smoke Emission

    IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

    CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

    No Toxic gases

    NES 02-713; NF C 20-454

    Note: Asterisk * denotes superseded standard.
    VOLTAGE RATING
    450/750V & 600/1000V
    CABLE CONSTRUCTION
    Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2
    Fire Barrier: Mica glass tape
    Insulation: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
    COLOUR CODE
    Insulation Colour: Orange (other colors upon request)
    Physical AND THERMAL PROPERTIES
    Temperature range during operation (fixed state): -30°C – +90°C
    Temperature range during installation (mobile state): -20°C – +50°C
    Minimum bending radius: 6 x Overall Diameter
    Electrical PROPERTIES

    Dielectric test:

    600/1000V: 3500 V r.m.s. x 5’ (core/core);
    450/750V: 2500 V r.m.s. x 5’ (core/core)

    Insulation resistance

    20 MΩ x km (at 20°C)

    Short circuit temperature

    250°C