    CALEDONIAN-FFX400 Fire Resistant 600/1000V Mica+XLPE Insulated, LSZH Sheathed Power & Control Cables (2-4 cores) 雲母耐火級XLPE + 低煙無毒電力控制電纜
    看原圖
    5542923




    商品編號: CALEDONIAN-FFX400

    CALEDONIAN-FFX400 Fire Resistant 600/1000V Mica+XLPE Insulated, LSZH Sheathed Power & Control Cables (2-4 cores) 雲母耐火級XLPE + 低煙無毒電力控制電纜


    APPLICATION

    This cable is designed for areas where the integrity of the electrical properties circuit is critical in
    maintaining power supply. Applications can be found in emergency lightings, control and power
    circuits, power stations, fire alarm systems, underground tunnels, communications systems, sewage
    treatment plants, lifts, escalators, and high-rise buildings.
    STANDARDS
    Basic design to IEC 60502-1/BS 7846




    ★★★★商品說明★★★★

    PRODUCTS

    Fire Resistant Power & Control Cables
    600/1000V Mica+XLPE Insulated, LSZH Sheathed Power Cables (2-4 cores)
    FFX400 1mRZ1-R (CU/MGT+XLPE/LSZH 600/1000V Class 2)
    FFX400 1mRMZ1-R (CU/MGT+XLPE/LSZH/SWA/LSZH 600/1000V Class 2)
    APPLICATION
    This cable is designed for areas where the integrity of the electrical properties circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, communications systems, sewage treatment plants, lifts, escalators, and high-rise buildings.
    STANDARDS
    Basic design to IEC 60502-1/BS 7846
    FIRE PERFORMANCE

    Circuit Integrity

    IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);

    CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);

    NF C32-070-2.3(CR1); BS 7846-(F2)

    System circuit integrity

    DIN 4102-12, E30 depending on lay system

    Flame Retardance (Single Vertical Wire Test)

    EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;

    VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

    CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

    Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

    EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

    Halogen Free

    IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

    CEI 20-37/2-1 ; BS 6425-1*

    No Corrosive Gas Emission

    IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

    CEI 20-37/2-2 ; BS 6425-2*

    Minimum Smoke Emission

    IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

    CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

    No Toxic gases

    NES 02-713; NF C 20-454

    Note: Asterisk * denotes superseded standard.
    VOLTAGE RATING
    600/1000V
    CABLE CONSTRUCTION
    Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
    Insulation: Mica glass tape covered by extruded cross-linked XLPE compound
    Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
    Inner Sheath(optional): Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1
    rmouring(optional): Galvanized steel wire armour
    Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
    COLOUR CODE
    Insulation Colour
    2 - Core: (Brown & Blue)
    3 - Core: (Brown, Black & Grey)
    4 - Core: (Brown, Black, Grey & Blue)
    Sheath Colour
    Orange (other colors upon request)
    Physical AND THERMAL PROPERTIES
    Temperature range during operation (fixed state): -30°C – +90°C
    Temperature range during installation (mobile state): -20°C – +50°C
    Minimum bending radius: 8 x Overall Diameter (unarmoured cable)
    10 x Overall Diameter (armoured cable)
    Electrical PROPERTIES

    Dielectric test:

    3500 V r.m.s. x 5’ (core/core)

    Insulation resistance

    1000 MΩ x km (at 20°C)

    Short circuit temperature

    250°C