1. CALEDONIAN-Fire Resistant Coaxial Cables 耐火級低煙無毒同軸電纜線
    CALEDONIAN-Fire Resistant Fire Alarm Cables (950°C 180 minutes)耐火級低煙無毒火警警報電纜線
    Caledonian-Fire Resistant Instrumentation Cables (950°C 180 minutes) 耐火級低煙無毒儀表控制電纜線
    CALEDONIAN-Fire Resistant Optic Fiber Cables 耐火級低煙無毒光纖電纜線
    Caledonian-Fire Resistant Power & Control Cables (950°C 180 minutes) 耐火級低煙無毒電力控制電纜線
    MICC/TRM/TET-Mineral Insulated Heating Units & Cable
    回上一頁
  2. 產品搜尋
    分 類:
    關鍵字:  

    首頁 > > Caledonian-Fire Resistant Power & Control Cables (950°C 180 minutes) 耐火級低煙無毒電力控制電纜線

    CALEDONIAN-FFX200 05SZ1-U Fire Resistant 300/500V SR Insulated Control Cables (2-4 Cores) 矽橡膠 + 低煙無毒電力控制電纜
    看原圖
    5542932




    商品編號: CALEDONIAN-FFX200-05SZ1-U

    CALEDONIAN-FFX200 05SZ1-U Fire Resistant 300/500V SR Insulated Control Cables (2-4 Cores) 矽橡膠 + 低煙無毒電力控制電纜


    CABLE CONSTRUCTION
    Conductors: Plain annealed copper wire, solid according to IEC(EN) 60228 class 1.
    Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.
    Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
    Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
     




    ★★★★商品說明★★★★

    PRODUCTS

    Fire Resistant Power & Control Cables
    300/500V SR Insulated Control Cables (2-4 Cores)
    FFX200 05SZ1-U (PH60) (CU/SR/LSZH 300/500V Class 1)
    APPLICATION
    The cables are designed, for use as control cable for emergency services and fire circuit control.
    STANDARDS
    Basic design adapted from BS 7629-1
    FIRE PERFORMANCE

    Circuit Integrity

    IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);

    BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)

    Circuit Integrity with mechanical shock

    EN 50200(PH60); CEI 20-36/4-0

    Circuit Integrity with mechanical shock & water spray

    EN 50200 annex E

    System circuit integrity

    DIN 4102-12, E30 depending on lay system

    Flame Retardance (Single Vertical Wire Test)

    EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;

    VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

    Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

    EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

    Halogen Free

    IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

    CEI 20-37/2-1 ; BS 6425-1*

    No Corrosive Gas Emission

    IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

    CEI 20-37/2-2 ; BS 6425-2*

    Minimum Smoke Emission

    IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

    CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

    No Toxic gases

    NES 02-713; NF C 20-454

    Note: Asterisk * denotes superseded standard.
    VOLTAGE RATING
    300/500 V
    CABLE CONSTRUCTION
    Conductors: Plain annealed copper wire, solid according to IEC(EN) 60228 class 1.
    Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.
    Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
    Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
    COLOUR CODE
    Insulation Colour
    Without earth conductor
    2 cores black - blue
    3 cores black - blue - brown
    4 cores black - blue - brown - black
    With earth conductor
    3 cores black - blue - yellow/green
    4 cores black - blue - brown - yellow/green
    Sheath Colour: Orange (other colors upon request)
    Physical AND THERMAL PROPERTIES
    Temperature range during operation (fixed state): -30°C – +90°C
    Temperature range during installation (mobile state): -20°C – +50°C
    Minimum bending radius: 6 x Overall Diameter
    Electrical PROPERTIES

    Dielectric test:

    2000 V r.m.s. x 5’ (core/core)

    Insulation resistance

    ≥300 MΩ x km (at 20°C)

    Short circuit temperature

    350°C