1. An-Armor Cable Teck 90 & Accessories 金屬鎧裝電纜
    An-Armor Cable 1 金屬鎧裝電纜
    An-BuildingWire(建築線)
    An-Crane Festoon and Reeling Cable
    An-INDUSTRIAL TRAY CABLE (TC)
    An-Instrumentation & Tray Cable [ Industrial / Special Applications Cables - 150°C to 260°C ]
    An-Instrumentation Cable 儀俵控制電纜
    An-MINING CABLE(Thermoset Jacket)採礦業機械馬達用線(軟質)
    An-Portable Cord 輕便電纜
    An-Power Cable1 電力電纜
    An-Power Cable2 電力電纜
    An-Power Cable3 電力電纜
    An-PVC-Nylon/PVC Control Cable PVC尼龍被覆控制電纜-1
    An-PVC-Nylon/PVC Control Cable PVC尼龍被覆控制電纜-2
    An-PVC-Nylon/PVC Shielded Control Cable PVC尼龍被覆鋁箔隔離控制電纜
    An-PVC-Nylon/PVC-Nylon Control Cable PVC尼龍絕緣PVC尼龍被覆控制電纜
    An-Security Low-voltage Cable 低壓安全監控用線
    An-TRAFFIC SIGNAL CABLE 交通號誌控制電纜
    回上一頁
  2. 產品搜尋
    分 類:
    關鍵字:  

    首頁 > > An-Instrumentation Cable 儀俵控制電纜

    TC 600V EPR/CPE SHIELDED  MULTI PAIR 隔離對型 儀俵控制電纜
    看原圖
    5258094

    商品編號: A-2MR-1601POS

    2MR-1601POS TC 600V EPR/CPE SHIELDED MULTI PAIR 隔離對型 儀俵控制電纜


    For use indoors or outdoors and for installationin trays, troughs, channels, ducts and directburial. Designed for telemetering, signals, relaysand communication.

    EPR/CPE
    SHIELDED
    MULTI PAIR
    EPR Insulation
    CPE Jacket
    90°C, 600 Volt


    APPLICATIONS:
    For use indoors or outdoors and for installation
    in trays, troughs, channels, ducts and direct
    burial. Designed for telemetering, signals, relays
    and communication.
     

    SPECIFICATIONS:
    1. CONDUCTORS:
    Annealed, tinned copper in accordance with ASTM B-3 and B-33.
    Concentric stranded, Class B per ASTM B-8.
    2. INSULATION: Ethylene propylene rubber (EPR), per ICEA S-68-516. UL rated VW-1 conductors.
    3. PAIRS/TRIADS: Each pair/triad is twisted to a 2 in. lay. Color coded: pairs black/white,
    triads black/white/red with alphanumeric designation (1-ONE).
    4. ASSEMBLY: The individually shielded pairs are cabled together with non-hygroscopic
    and flame retardant fillers as necessary to form a circular cross section of the assembly.
    A binding tape, when required, shall be applied over cable core.
    5. SHIELDING: The entire cable assembly is shielded with polyester backed/aluminum tape
    and tinned copper drain wire.
    6. OVERALL JACKET: Flame retardant chlorinated polyethylene (CPE).
    7. STANDARDS: Meets the requirements of UL 1277. Finished cable passes UL 1581
    70,000 BTU and ICEA T-29-520, 210,000 BTU flame tests. UL listed as sunlight resistant
    and rated for direct burial.
    8. TEMPERATURE: 90°C
    9. VOLTAGE: 600 Volts