TelcoFlex® II TelcoHyde®. Class I Flexible Strand LSNH, UL Listed RHH/ST1 Central Office Power Wire and Cable 低煙無鹵軟質中央辦公室電源線和電纜
Central Office Power Wire and Cable
Class I Flexible Strand Without Braid
Low Smoke, Non-Halogenated Insulation, Lead-Free and Silicone-Free, UL Central Office Power Cable. 105° Dry as AWM, 60°C Wet; UL Listed RHH/ST1 90°C Dry, 60°C Wet, 600 Volts. Sizes 1/0 AWG and larger are UL Listed for CT USE. CSA AWM I B 105°C 600 Volt FT4.
Scope
This specification covers the construction requirements for low smoke, non-halogenated central office power wire and cable, insulated with Southwire TelcoHyde®. UL listed Type RHH/ST1 for use in accordance with the National Electrical Code. The construction of the wire and cable is in accordance with Telcordia GR-347-CORE and KS-24194™ and ATIS-0600017.2014, Underwriters’ Laboratories requirements, and the requirements of CSA for the FT4 flame test. Sizes 1/0 AWG and larger are UL “CT Use” (Cable Tray) rated.
Construction
Size: Sizes 14 AWG through 750 KCMIL • Single conductor.
Conductors: Class I (modified) bunched (8 and 6 AWG) and rope-bunched (4 AWG and larger) stranded tinned copper conforming to ASTM B-33 and Underwriters’ Laboratories requirements. An opaque Mylar tape shall be applied over the conductor to facilitate stripping. Class K copper used with 14-10 AWG.
Insulation: 105°C rated low smoke, non-halogen TelcoHyde® conforming to Underwriters’ Laboratories Standard 44, Subjects 509 and 758, and CSA C22.2 No. 210-11. In addition, TelcoHyde® complies with the requirements of Telcordia Specification GR-347-CORE. The insulation has a Limiting Oxygen Index of 35%.
Surface Marking: Two sides of the cable shall be printed using an ink of contrasting color and with the following information: “SOUTHWIRE AIW™ CORD BRAND TELCOFLEX® II/KS24194™ L2 NON-HAL (UL) E18321 SIZE (AWG or KCMIL) 600 VOLTS RHH ST1 FT4 OR AWM 3578 60°C WET VW-1 — LL8825 CSA AWM I B 105°C 600 VOLTS FT4-ST1 YEAR TIME JULIAN DATE — MEETS IEC INCLUDING 60674 & 60332”.
Note: KS24194™ L2 printed on 8-750 only. For sizes 1/0 AWG and larger add “FOR CT USE” before “(AWM 3578)” on Sizes 1/0 AWG and larger. Sequential footage markings shall be applied at 2 foot intervals on one side of the cable.
Testing: Physical and electrical tests in accordance with UL Standard 44 requirements, Subject 509 and 758; and CSA Standard C22.2 No. 210-11 as AWM.
Labels: UL tags and labels shall be applied to all packages
Cable Data
SIZE |
STRANDING |
NOMINAL CMA |
CONDUCTOR DIAMETER (INCHES) |
INSUL. MIN. AVG. WALL (MILS) |
NOMINAL INSUL. DIAM. (INCHES) |
MAX D.C. RES. @ 20° C (OHMS/MFT) |
AMPACITY PER NEC TABLE 310.15 (B)(16)
|
|
75° C |
90° C |
14 |
41 |
4110 |
.077 |
45 |
.170 |
2.730 |
20 |
25 |
12 |
65 |
6530 |
.089 |
45 |
.182 |
1.720 |
25 |
30 |
10 |
104 |
10380 |
.116 |
45 |
.209 |
1.080 |
35 |
40 |
8 |
41 |
16510 |
.153 |
60 |
.280 |
.6790 |
50 |
55 |
6 |
65 |
26240 |
.188 |
60 |
.315 |
.4360 |
65 |
75 |
4 |
105 |
41740 |
.260 |
60 |
.385 |
.2740 |
85 |
95 |
2 |
168 |
66360 |
.305 |
60 |
.430 |
.1720 |
115 |
130 |
1 |
224 |
83690 |
.370 |
80 |
.540 |
.1260 |
130 |
150 |
1/0 |
266 |
105600 |
.392 |
80 |
.560 |
.1090 |
150 |
170 |
2/0 |
342 |
133100 |
.455 |
80 |
.620 |
.0868 |
175 |
195 |
4/0 |
542 |
211600 |
.577 |
80 |
.745 |
.0546 |
230 |
260 |
350 |
888 |
350000 |
.760 |
95 |
.960 |
.0334 |
310 |
350 |
500 |
1221 |
500000 |
.890 |
95 |
1.090 |
.0234 |
380 |
430 |
750 |
1850 |
750000 |
1.094 |
110 |
1.320 |
.0157 |
475 |
535 |