TelcoSafe® LIST 1, UL44, RHH/RHW/ST1, ROHS, Central Office Power Wire and Cable 中央辦公室電源線和電纜
Limited Smoke, Non-Halogenated Insulated, Silicone-Free, Lead-Free
Meets European RoHS directive
90°C Dry, 75°C Wet – 600 Volts DC or AC
UL Listed RHH/RHW/ST1 and VW-1 (8 AWG and Larger)
UL Listed “For CT Use” (1/0 AWG and Larger)
CSA Listed AWM I A/B, 105°C, 1000 Volts, FT1, FT2
FT4-ST1, -40°C, W75C
Audited by Telcordia to all 33 requirements of GR-347-CORE
Meets IEC including 60674 & 60332
Scope
This specification covers the construction requirements for limited smoke,
non-halogenated Central Office Power Wire and Cable, insulated with a
proprietary EVA Copolymer limited smoke, non-halogenated compound. UL
listed Type RHH/RHW/ST1, for use in accordance with the National Electrical
Code.
The construction of the wire and cable is in accordance with Underwriters’
Laboratories requirements and the requirements of CSA for the FT4/ST1
flame/smoke test. Sizes 1/0 AWG and larger are UL “CT Use” (Cable Tray)
rated.
Construction
Size (AWG OR KCMIL) |
Stranding |
Conductor Diameter (Inches) |
Insulation Min. Avg. Wall (mils) |
Nominal Insulation Diam. (Inches) |
14 |
solid |
.0641 |
45 |
.160 |
12 |
solid |
.0808 |
45 |
.175 |
14 |
7/.0242” |
.071 |
45 |
.165 |
12 |
7/.0305” |
.090 |
45 |
.185 |
10 |
7/.0385” |
.114 |
45 |
.210 |
8 |
7/.0486” |
.143 |
60 |
.270 |
6 |
7/.0612” |
.180 |
60 |
.305 |
4 |
7/.0772” |
.227 |
60 |
.350 |
2 |
7/.0974” |
.286 |
60 |
.410 |
1 |
19/.0664” |
.332 |
80 |
.493 |
1/0 |
19/.0745” |
.365 |
80 |
.530 |
2/0 |
19/.0837” |
.411 |
80 |
.575 |
4/0 |
19/.1055” |
.517 |
80 |
.680 |
350 |
37/.0973” |
.667 |
95 |
.860 |
500 |
37/.1162” |
.797 |
95 |
.990 |
750 |
61/.1109” |
.978 |
110 |
1.200 |
1000 |
61/.1280″ |
1.134 |
110 |
1.370 |
Size: 14 AWG Through 1000 KCMIL – Single Conductor
Conductors: Class B concentric stranded or solid, tinned copper conforming to ASTM B-8 or B-3 and B-33 and Underwriters’ Laboratories requirements. An opaque mylar tape shall be applied over the conductor to facilitate stripping.
Insulation: Black EVA Copolymer limited smoke, non-halogen, lead-free compound conforming to Underwriters’ Laboratories Standard 44, Subjects 509 and 758, and CSA C22.2 No. 210-2-M90. The insulation has a limiting oxygen index (L.O.I.) minimum of 28%. Other colors can be furnished upon request.
Surface Marking:Two sides of the cable shall be printed using an ink of contrasting color and
with the following information:
“SOUTHWIRE AIW™ CORD BRAND TELCOSAFE® L1 NON-HAL (UL) E18321
SIZE AWG 600 VOLTS RHH OR RHW/ST/1 FT4/IEEE1202 SR — LL90458 CSA
AWM I A/B 105°C 1000 VOLTS W75C -40°C FT1, FT2, FT4-ST1 (YEAR of MFG)
— MEETS IEC INCLUDING 60674 & 60332 — (SEQ. FOOTAGE. ON 1 SIDE)”
For Sizes 1/0 AWG and larger add, “FOR CT USE” before “(UL)”
For Sizes 8 AWG and larger add, “VW-1” after “(UL)”
Testing: Physical and electrical tests in accordance with the requirements of UL Standard 44, Subject 509 and 758, and CSA Standard C22.2 No. 210.2-M90 as AWM.