    首頁 > > An-Power Cable2 電力電纜

    EPR/PVC Copper Tape Shield 100% Insulation Level 35KV 105°C 銅帶隔離高壓電力電纜
    看原圖
    5266024

    商品編號: A-3DX-1011

    EPR/PVC Copper Tape Shield 100% Insulation Level 35KV 105°C 銅帶隔離高壓電力電纜
     

    For use in power circuits up to 35 kV when installed in open air, conduit, duct or direct burial for wet or dry locations. Used for power applications in chemical plants,
    refineries, steel mills, industrial plants, utility substations and generating stations.

    Power Cable


    35 kV - 100% Insulation Level

    EPR/PVC Copper Tape Shield

    EPR insulation
    PVC jacket
    Shielded
    100% insulation level


    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, annealed copper per ASTM B-3 and B-8, strand shield is an extruded semiconducting thermoset
    2. INSULATION: Ethylene Propylene Rubber (EPR) per ICEA S-93-639 (NEMA WC74)
    3. INSULATION SHIELD: Extruded semiconducting thermoset insulation shield. Metallic shield is a helically applied 5 mil uncoated copper shielding tape
    4. OVERALL JACKET: Sunlight-resistant, black Polyvinyl Chloride (PVC)
    5. STANDARDS: Listed as Type MV-105 per UL 1072 and meets the requirements of ICEA S-93-639. Sizes 1/0 and larger pass UL 1685 70,000 Btu/hr flame test
    6. AMPACITY: Based on three single conductor cables in isolated conduit in air per NEC Table 310.73 with a conductor temperature of 90°C and an ambient temperature of 40°C
    7. TEMPERATURE: 105°C
    8. VOLTAGE:35 kV


    APPLICATIONS
    For use in power circuits up to 35 kV when installed in open air, conduit, duct or direct burial for wet or dry locations. Used for power applications in chemical plants,