商品編號: Belden-8473
8473 Paired - High-Conductivity Copper Speaker Cable 廣播聲音音響, 儀表控制電纜
14 AWG stranded (42x30) tinned copper conductors, PVC insulation, twisted pair, PVC jacket.
8473
|
|
Multi-Conductor - High-Conductivity Copper Speaker Cable Twisted Jacketed Con
14 AWG stranded (42x30) tinned copper conductors, PVC insulation, twisted pair, PVC jacket. |
For more Information
please call
1-800-Belden1 |
Item # |
Putup |
Ship Weight |
Color |
Notes |
Item Desc |
8473 060U500 |
500 FT |
29.000 LB |
CHROME |
|
1 PR #14 PVC PVC |
8473 0601000 |
1,000 FT |
58.000 LB |
CHROME |
C |
1 PR #14 PVC PVC |
8473 060500 |
500 FT |
30.500 LB |
CHROME |
C |
1 PR #14 PVC PVC |
|
Notes: |
|
C = CRATE REEL PUT-UP.
|
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs |
AWG |
Stranding |
Conductor Material |
1 |
14 |
42x30 |
TC - Tinned Copper |
|
Insulation
Insulation Material:
Insulation Material |
Wall Thickness (in.) |
PVC - Polyvinyl Chloride |
.031 |
|
Insulation Resistance: |
1000 Megohms/1000 ft. @ 500 VDC |
Outer Shield
Outer Shield Material:
Outer Shield Material |
Unshielded |
|
Outer Jacket
Outer Jacket Material:
Outer Jacket Material |
Nom. Wall Thickness (in.) |
PVC - Polyvinyl Chloride |
.032 |
|
Overall Cabling
Overall Nominal Diameter: |
0.340 in. |
Pair
Pair Color Code Chart:
Number |
Color |
1 |
Black & White |
|
Pair Lay Length & Direction:
Lay Length (in.) |
Twists/ft. (twist/ft) |
2.000 |
6.000 |
|
Mechanical Characteristics (Overall)
Operating Temperature Range: |
-20°C To +90°C |
Non-UL Temperature Rating: |
90°C (UL AWM Style 2587) |
Bulk Cable Weight: |
52.600 lbs/1000 ft. |
Max. Recommended Pulling Tension: |
94 lbs. |
Min. Bend Radius (Install)/Minor Axis: |
3.500 in. |
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: |
CL3 |
AWM Specification: |
UL Style 2587 (600 V 90°C) |
EU Directive 2000/53/EC (ELV): |
Yes |
EU Directive 2002/95/EC (RoHS): |
Yes |
EU RoHS Compliance Date (mm/dd/yyyy): |
04/01/2005 |
EU Directive 2002/96/EC (WEEE): |
Yes |
EU Directive 2003/11/EC (BFR): |
Yes |
CA Prop 65 (CJ for Wire & Cable): |
Yes |
MII Order #39 (China RoHS): |
Yes |
Flame Test
UL Flame Test: |
UL1685 UL Loading |
Plenum/Non-Plenum
Electrical Characteristics (Overall)
Nom. Inductance:
Nom. Capacitance Conductor to Conductor:
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft) |
2.86 |
|
Max. Operating Voltage - UL:
Voltage |
Description |
600 V RMS |
UL AWM Style 2587 |
300 V RMS |
CL3 |
|
Max. Recommended Current:
Current |
9.6 Amps per conductor @ 25°C (10°C rise in temp) |
|
Notes (Overall)
Notes: |
Nominal Breakdown Voltage - Jacket 20 KV RMS; Nominal Breakdown Voltage Between Conductors 25 KV RMS. See NEC guidelines for applicable CL3 voltage ratings. |
|
|
|
|
|