9875  | | Multi-Conductor - Audio, Control and Instrumentation Cable 20 AWG stranded (7x28) TC conductors, polypropylene insulation, twisted pairs, individually shielded w/Beldfoil® (100% coverage), 22 AWG stranded TC drain wire, overall PVC jacket. | For more Information please call 1-800-Belden1 |
| Item # | Putup | Ship Weight | Color | Notes | Item Desc | | 9875 060100 | 100 FT | 17.700 LB | CHROME | C | 9 FS PR #20 PP PVC | | 9875 0601000 | 1,000 FT | 165.000 LB | CHROME | C | 9 FS PR #20 PP PVC | | 9875 060500 | 500 FT | 87.500 LB | CHROME | C | 9 FS PR #20 PP PVC | |
| Notes: | |
C = CRATE REEL PUT-UP. |
Physical Characteristics (Overall)
Conductor
AWG:
| # Pairs | AWG | Stranding | Conductor Material | | 9 | 20 | 7x28 | TC - Tinned Copper | |
Insulation
Insulation Material:
| Insulation Material | | PP - Polypropylene | |
Inner Shield
Inner Shield Material:
| Inner Shield Trade Name | Type | Inner Shield Material | Coverage (%) | | Beldfoil® (Z-Fold®) | Tape | Aluminum Foil-Polyester Tape | 100 | |
Inner Shield Drain Wire AWG:
| Inner Shield Drain Wire Stranding: | 19x34 |
| Inner Shield Drain Wire Conductor Material: | TC - Tinned Copper |
Outer Jacket
Outer Jacket Material:
| Outer Jacket Material | | PVC - Polyvinyl Chloride | |
Overall Cabling
| Overall Nominal Diameter: | 0.555 in. |
Pair
Pair Color Code Chart:
| Number | Color | | 1 | Black & Red | | 2 | Black & White | | 3 | Black & Green | | 4 | Black & Blue | | 5 | Black & Yellow | | 6 | Black & Brown | | 7 | Black & Orange | | 8 | Red & White | | 9 | Red & Green | |
Pair Lay Length & Direction:
| Lay Length (in.) | Twists/ft. (twist/ft) | | 1.750 | 6.850 | |
Mechanical Characteristics (Overall)
| Operating Temperature Range: | -20°C To +80°C |
| UL Temperature Rating: | 80°C (UL AWM Style 2919) |
| Bulk Cable Weight: | 157.210 lbs/1000 ft. |
| Max. Recommended Pulling Tension: | 320 lbs. |
| Min. Bend Radius (Install)/Minor Axis: | 5.500 in. |
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
| NEC/(UL) Specification: | CM |
| CEC/C(UL) Specification: | CM |
| AWM Specification: | UL Style 2919 (30 V 80°C) |
| EU Directive 2000/53/EC (ELV): | Yes |
| EU Directive 2002/95/EC (RoHS): | Yes |
| EU RoHS Compliance Date (mm/dd/yyyy): | 01/01/2004 |
| EU Directive 2002/96/EC (WEEE): | Yes |
| EU Directive 2003/11/EC (BFR): | Yes |
| CA Prop 65 (CJ for Wire & Cable): | Yes |
| MII Order #39 (China RoHS): | Yes |
Flame Test
| UL Flame Test: | UL1685 UL Loading |
Plenum/Non-Plenum
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Nom. Inductance:
Nom. Capacitance Conductor to Conductor:
Nom. Capacitance Cond. to Other Conductor & Shield:
Nominal Velocity of Propagation:
Nom. Conductor DC Resistance:
| DCR @ 20°C (Ohm/1000 ft) | | 10.5 | |
| Ind. Pair Nominal Shield DC Resistance @ 20 Deg. C: | 11.300 Ohm/1000 ft |
Max. Operating Voltage - UL:
| Voltage | | 30 V RMS (UL AWM Style 2919) | | 300 V RMS (CM) | |
Max. Recommended Current:
| Current | | 2.0 Amps per conductor @ 25°C | |