商品編號: Belden-3095A
Belden3095A Plenum RG-11/U Type ControlBus™ Quad Shielded Coax 自動化工業電腦Controlnet™控制資料傳輸線
DESCRIPTION:
14 AWG solid bare copper-covered steel conductor, foam FEP insulation, Duobond® IV Quad Shield (100% coverage), fluorocopolymer Jacket.
SUITABLE APPLICATIONS :
Suitable Applications: Plenum RG-11/U Type
PHYSICAL CHARACTERISTICS :
CONDUCTOR :
Number of Coax: 1
Total Number of Conductors: 1
RG Type: 11/U
AWG: 14
Stranding: Solid
Conductor Diameter: .064 in.
Conductor Material: BCCS - Bare Copper Covered Steel
INSULATION :
Insulation Material: FFEP - Foam Fluorinated Ethylene Propylene
Insulation Diameter: .280 in.
OUTER SHIELD :
Outer Shield Material Trade Name: Duobond® IV
Outer Shield Type: Tape/Braid/Tape/Braid
Outer Shield Material:
Layer Number Trade Name Type Material % Coverage (%)
1 Bonded Duofoil® Tape Bonded Aluminum Foil-Polyester Tape-Aluminum Foil 100
2 Braid AL - Aluminum 60
3 Duofoil® Tape Aluminum Foil-Polyester Tape-Aluminum Foil 100
4 Braid AL - Aluminum 40
Outer Shield %Coverage: 100 %
OUTER JACKET :
Outer Jacket Material: PVDF - Fluorocopolymer
OVERALL NOMINAL DIAMETER :
Overall Nominal Diameter: .387 in.
MECHANICAL CHARACTERISTICS :
Operating Temperature Range: -20°C To +150°C
Non-UL Temperature Rating: 150°C
Bulk Cable Weight: 68 lbs/1000 ft.
Max. Recommended Pulling Tension: 309 lbs.
Min. Bend Radius (Install): 4 in.
APPLICABLE SPECIFICATIONS AND AGENCY COMPLIANCE :
APPLICABLE STANDARDS :
NEC/(UL) Specification: CMP
CEC/C(UL) Specification: CMP
EU RoHS Compliant (Y/N): Yes
EU RoHS Compliance Date (mm/dd/yyyy):: 01/01/2004
FLAME TEST :
UL Flame Test: NFPA 262
CSA Flame Test: FT6
SUITABILITY :
Suitability - Outdoor: Yes
Suitability - Burial: Yes
PLENUM/NON-PLENUM :
Plenum (Y/N): Y
Non-Plenum Number: 3094A
ELECTRICAL CHARACTERISTICS :
Nom. Characteristic Impedance: 75 +/- 3 Ω
Nom. Inductance: .097 µH/ft
Nom. Capacitance Conductor to Shield: 16.5 pF/ft
Nominal Velocity of Propagation: 82 %
Nominal Delay: 1.2 ns/ft
Nom. Conductor DC Resistance @ 20 Deg. C: 11.0 Ω/1000 ft
Nominal Outer Shield DC Resistance @ 20 Deg.C: 3.9 Ω/1000 ft
Minimum Structural Return Loss:
Description Frequency (MHz) Start Frequency (MHz) Stop Frequency (MHz) Minimum Structural Return Loss (dB)
5 400 20
Nom. Attenuation:
Description Frequency (MHz) Start Frequency (MHz) Stop Frequency (MHz) Nom. Attenuation (dB/100 ft.)
1 .17
2 .22
5 .28
10 .40
20 .60
50 1.20
100 1.70
200 2.50
300 3.04
400 3.50
Max. Operating Voltage - UL: 300 V RMS
Phase Delay Distortion:
F/B %PDD/100M (5MB) %PDD/100M (10MB)
0.5 -0.60 -1.27
1.0 -0.46 -0.43
1.5 0 0
F/B %PDD/100M (5MB) %PDD/100M (10MB)
2.0 +0.17 +0.27
2.5 +0.30 +0.45
Other Electrical Characteristic 1: Tilt 5 to 10 MHz: .42 dB/100 M
Other Electrical Characteristic 2: Tilt 10 to 20 MHz: .58 dB/100 M
NOTES :
Notes: Sweep tested 5 to 400 MHz. Tap marks every 2.6 meters to aid users in installation.
PUT-UPS AND COLORS:
Item Description Put-Up (ft.) Ship Weight (lbs.) Jacket Color Notes
3095A F2V1000 #14 FFEP DBSH SLF 1000 76 GRAY, DEC C
C = CRATE REEL PUT-UP.
|
|
|
|
|