 | | Multi-Conductor - Audio, Control, Communication and Instrumentation Cable 20 and 16 AWG stranded (7x28 and 19x28) tinned copper conductors, conductors cabled, PVC insulation, PVC jacket. | For more Information please call
1-800-Belden1 |
| Item # | Putup | Ship Weight | Color | Notes | Item Desc |
|
Physical Characteristics (Overall)
Conductor
AWG:
| # Conductors | AWG | Stranding | Conductor Material | | 3 | 20 | 7x28 | TC - Tinned Copper | | 3 | 16 | 19x28 | TC - Tinned Copper |
|
Insulation
Insulation Material:
| Insulation Trade Name | Dia. (in.) | AWG | | PVC - Polyvinyl Chloride | .012 | 20 | | PVC - Polyvinyl Chloride | .013 | 16 |
|
| Insulation Resistance: | 100 Mega Ohms/1000 ft. @ 500 V DC |
Outer Shield
Outer Shield Material:
| Outer Shield Material | | Unshielded |
|
Outer Jacket
Outer Jacket Material:
| Outer Jacket Material | Nom. Wall Thickness (in.) | | PVC - Polyvinyl Chloride | .032 |
|
Overall Cabling
Overall Cabling Lay Length & Direction:
| Length (in.) | Twists (ft.) | | 6.0 | 2 |
|
Overall Cabling Color Code Chart:
| Number | Color | AWG | Group/Cond. Color | | 1 | 20-Green | 20 | Green | | 2 | Blue | 20 | Blue | | 3 | Purple. 16-Black | 20 | Purple | | 1 | Red | 16 | Black | | 2 | Yellow | 16 | Red | | 3 | | 16 | Yellow |
|
| Overall Nominal Diameter: | 0.295 in. |
Mechanical Characteristics (Overall)
| Operating Temperature Range: | -20°C To +60°C |
| Non-UL Temperature Rating: | 90°C |
| Bulk Cable Weight: | 63.100 lbs/1000 ft. |
| Max. Recommended Pulling Tension: | 133.200 lbs. |
| Min. Bend Radius (Install)/Minor Axis: | 3 in. |
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
| NEC/(UL) Specification: | CM |
| EU Directive 2000/53/EC (ELV): | Yes |
| EU Directive 2002/95/EC (RoHS): | Yes |
| EU RoHS Compliance Date (mm/dd/yyyy): | 04/01/2005 |
| EU Directive 2002/96/EC (WEEE): | Yes |
| EU Directive 2003/11/EC (BFR): | Yes |
| CA Prop 65 (CJ for Wire & Cable): | Yes |
| MII Order #39 (China RoHS): | Yes |
Flame Test
| UL Flame Test: | UL1685 UL Loading |
Plenum/Non-Plenum
Electrical Characteristics (Overall)
Nom. Inductance:
| Description | Inductance (µH/ft) | | 20 AWG | .318 | | 16 AWG | .195 |
|
Nom. Capacitance Conductor to Conductor:
| Description | Freq. (MHz) | Capacitance (pF/ft) | | 20 AWG | 1 | 20 | | 16 AWG | 1 | 30 |
|
Nom. Capacitance Cond. to Other Cond. & Ground:
| Description | Capacitance (pF/ft) | | 20 AWG | 36 | | 16 AWG | 54 |
|
Nom. Conductor DC Resistance:
| Description | DCR @ 20°C (Ohm/1000 ft) | | 20 AWG | 10.25 | | 16 AWG | 4.07 |
|
Max. Operating Voltage - UL:
Max. Recommended Current:
| Current | | 3.2 Amps per conductor @ 25°C (20 AWG); 5.6 Amps per conductor @ 25°C (16 AWG) |
|