Armored Cable
Teck 90 (CSA)
15 kV Three Conductor 100% Insulation Level
Galvanized steel or interlocked aluminum armor
Shielded
XLP insulation
Inner and outer PVC jackets
100% insulation level
SPECIFICATIONS
1. CONDUCTOR: Class B stranded, bare, soft copper
2. CONDUCTOR SHIELD: Cables have a semiconducting shield over the conductor
3. INSULATION: Cross-Linked Polyethylene (XLP), 175 mils insulation thickness
4. IDENTIFICATION: The insulated conductors are identified by means of a colored tape (black, red and blue) placed longitudinally immediately under the copper tape shield
5. INSULATION SHIELD: Consists of a semiconducting thermosetting layer plus an overlaying metallic component, in multiconductor cables the metallic component is a helically
applied lapped copper tape
6. GROUNDING CONDUCTOR: An uninsulated Class B stranded grounding conductor is included in the cable assembly with suitable fillers
7. INNER JACKET: Polyvinyl Chloride (PVC)
8. ARMOR: Aluminum or galvanized steel interlocking armor
9. OUTER JACKET: Polyvinyl Chloride (PVC) heat-, flame- and moisture-resistant jacket, rated -40°C, the standard color is red but colored jackets are available on request
10.STANDARDS:The cable is certified to CSA C22.2 No. 131 and No. 174 for use in CSA Class 1, Division 1 hazardous locations (CSA HL rated) and CSA C68.3 and passes the
FT4 vertical tray flame test
11.AMPACITY: Refer to IEEE 835-1994 tables for ampacity values, and the Canadian Electrical Code for correction factors
12.TEMPERATURE: -40°C to 90°C
13.VOLTAGE: 15 kV
APPLICATIONS
For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet or dry
locations. For direct earth burial.