    首頁 > > An-Armor Cable Teck 90 & Accessories 金屬鎧裝電纜

    A-Teck 90 (CSA) XLPE/Galv. Steel or Aluminum Armor/PVC  100% Insulation Level Shielded 15KV 3芯耐高壓波紋鋁管or波紋鋼管鎧裝電力控制電纜
    看原圖
    5260322




    商品編號: A-7TP-0203

    A-Teck 90 (CSA) XLPE/Galv. Steel or Aluminum Armor/PVC 100% Insulation Level Shielded 15KV 3芯耐高壓波紋鋁管or波紋鋼管鎧裝電力控制電纜


    For exposed or concealed wiring in wet or drylocations. For use in ventilated, non-ventilated andladder type cable troughs and ventilatedflexible cableway in wet or dry locations.For direct earth burial.



    ★★★★商品說明★★★★

    Armored Cable
     

    Teck 90 (CSA)

    15 kV Three Conductor 100% Insulation Level

    Galvanized steel or interlocked aluminum armor
    Shielded
    XLP insulation
    Inner and outer PVC jackets
    100% insulation level
     

    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, bare, soft copper
    2. CONDUCTOR SHIELD: Cables have a semiconducting shield over the conductor
    3. INSULATION: Cross-Linked Polyethylene (XLP), 175 mils insulation thickness
    4. IDENTIFICATION: The insulated conductors are identified by means of a colored tape (black, red and blue) placed longitudinally immediately under the copper tape shield
    5. INSULATION SHIELD: Consists of a semiconducting thermosetting layer plus an overlaying metallic component, in multiconductor cables the metallic component is a helically
    applied lapped copper tape
    6. GROUNDING CONDUCTOR: An uninsulated Class B stranded grounding conductor is included in the cable assembly with suitable fillers
    7. INNER JACKET: Polyvinyl Chloride (PVC)
    8. ARMOR: Aluminum or galvanized steel interlocking armor
    9. OUTER JACKET: Polyvinyl Chloride (PVC) heat-, flame- and moisture-resistant jacket, rated -40°C, the standard color is red but colored jackets are available on request
    10.STANDARDS:The cable is certified to CSA C22.2 No. 131 and No. 174 for use in CSA Class 1, Division 1 hazardous locations (CSA HL rated) and CSA C68.3 and passes the
    FT4 vertical tray flame test
    11.AMPACITY: Refer to IEEE 835-1994 tables for ampacity values, and the Canadian Electrical Code for correction factors
    12.TEMPERATURE: -40°C to 90°C
    13.VOLTAGE: 15 kV


    APPLICATIONS
    For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet or dry
    locations. For direct earth burial.