    Lead-free EPR/PVC Copper Tape Shield 133% Insulation Level 5KV 銅帶隔離高壓電力電纜
     

    For use in power circuits up to 8 kV when installed in open air, conduit, duct or buried directly in the earth, for wet and dry locations. Used for power applications in chemical
    plants, refineries, steel mills, industrial plants, utility substations and generating stations.

    Power Cable
    5 kV Single Conductor - Shielded

    Lead-free EPR/PVC Copper Tape Shield

    EPR insulation
    PVC jacket
    Shielded
    133% insulation level
    Lead-free
    No lube required


    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, annealed, bare copper per ASTM B3 and B8, (compact stranding per ASTM B-496 is available), strand shield is an extruded conducting
    thermosetting compound
    2. INSULATION: Ethylene Propylene Rubber (EPR) per ICEA S-93-639 (NEMA WC74)
    3. INSULATION SHIELD:Over the insulation is an extruded semi-conducting, thermosetting insulation shield. Metallic shield is a helically applied 5 mil uncoated copper tape
    4. OVERALL JACKET:Sunlight-resistant black Polyvinyl Chloride (PVC), meeting the requirements of ICEA and UL 1072. Lubricant built into jacket to facilitate installation
    5. STANDARDS: Listed as Type MV-105 per UL 1072, meets the requirements of ICEA S-93-639, sizes 1/0 and larger marked "for CT use" and pass UL 1685 70,000 Btu/hr
    flame test
    6. AMPACITY:Based on three single conductor cables in isolated conduit in air per NEC Table 310.73 with a conductor temperature of 90°C and an ambient temperature of 40°C
    7. TEMPERATURE: 105°C
    8. VOLTAGE: 5 kV 133% and 8 kV 100%


    APPLICATIONS
    For use in power circuits up to 8 kV when installed in open air, conduit, duct or buried directly in the earth, for wet and dry locations. Used for power applications in chemical
    plants, refineries, steel mills, industrial plants, utility substations and generating stations.