| 商品編號: A-RHH-ST1-KS24194L2
A-RHH/ST1 KS24194 L2 Telecom Cable Non braided 600V 105°C dry, 60°C wet 電信用電力電纜
Telecommunications power cable. The cables are designed for use in 600 V AC or DC circuits in telecommunications central offices, wireless sites, repeater stations, data centers and other UPS and power management systems. The cable can be installed in trays, racks, or conduit in horizontal and vertical applications. |
| |
| | |
玉山 / 台新 / 華南 / 萬泰 / 兆豐 / 遠東 / 新光 / 永豐 / 第一 / 彰化 / 合庫 / 日盛 / 匯豐 / 渣打國泰世華 / 台北富邦 / 大眾銀行 / 台灣中小企銀/台中商銀 / 澳盛銀行
| |
| | |
| | Telecommunications power cable RHH/ST1 KS24194 L2 Non braided 600 V 105°C dry, 60°C wet SPECIFICATIONS 1. CONDUCTOR: Class I modified bunched (8 and 6 AWG) or rope-bunched (4 AWG and larger) stranded tin-coated copper conforming to ASTM B-33 and UL requirements, sizes 8 AWG thru 750 kcmil 2. INSULATION: 105°C rated limited smoke, zero halogen TelcoHyde 5221 conforming to UL Standards 44, 758 Subjects 509 and CSA C22.2 No.210.2 M90, in addition, TelcoHyde 5221 complies with the requirements of Telcordia Specification GR-347-CORE, the insulation has a Limiting Oxygen Index of 35% 3. FEATURES: An opaque aluminum/polyester tape shall be applied over the conductor to facilitate stripping, limited smoke, non-halogenated insulated 4. STANDARDS: UL Listed RHH/LS and VW-1 CSA for the FT4/ST1 flame/smoke test, sizes 1/0 AWG and larger are UL "for CT Use" (Cable Tray) rated, lead-free and silicone free, meets European RoHS directive, complies with Telcordia GR-347-CORE 5. TEMPERATURE: 105°C dry, 60°C wet 6. VOLTAGE: 600 V, FT4, ST1 |
| |
|
|