    首頁 > > An-INDUSTRIAL TRAY CABLE (TC)

    XLP/TS-CPE 90°C, 600 V Industrial Tray Cable UL XLPE 絕緣, TS-CPE 被覆工業控制電纜
    看原圖
    5257175

    商品編號: A-2RH-1403

    XLP/TS-CPE 90°C, 600 V Industrial Tray Cable UL XLPE 絕緣, TS-CPE 被覆工業控制電纜
     

    Designed for power and control, telemetering, relay control, traffic control, switching, lighting and signal transmission. May be used in Class I, Div. 2 and Class II Div 2
    Hazardous Locations per NEC Art. 501 and 502. These cables also conform to Art. 392 "Cable Trays" and Art. 336 "Power and Control Tray Cable: Type TC."

    Industrial Tray Cable

    XLP/TS-CPE

    XLP insulation
    TS-CPE jacket
    90°C, 600 V


    SPECIFICATIONS
    1. CONDUCTORS:
    Class B stranded tinned copper per ASTM B-3, B-8 and B-33
    2. INSULATION: Cross-Linked Polyethylene (XLPE) per ICEA S-73-532 (NEMA WC57), meets UL 44 requirements for VW-1, Type XHHW-2 conductors
    3. COLOR CODE: Conductors shall be color coded per ICEA Method 1, Table E-2 (formerly K-2)
    4. ASSEMBLY:Conductors are cabled with fillers where necessary to make round, two conductor cables are flat
    5. OVERALL JACKET:Sunlight-resistant Thermoset Chlorinated Polyethylene (TS-CPE) per UL 1277
    6. STANDARDS: Meets per UL 1277 requirements for Type TC cables having VW-1, XHHW-2 conductors, cables are listed for direct burial and meet the IEEE 1202, IEEE 383,
    and UL 1685. 70,000 Btu/hr flame tests as well as the ICEA T-29-520, 210,000 Btu/hr flame tests
    7. AMPACITY:Based on not more than three conductors in raceway or cable or earth with an ambient temperature of 30ºC and a conductor temperature of 90ºC per NEC 310.16,
    the values have been derated where applicable
    8. TEMPERATURE:90ºC
    9. VOLTAGE: 600 V


    APPLICATIONS
    Designed for power and control, telemetering, relay control, traffic control, switching, lighting and signal transmission. May be used in Class I, Div. 2 and Class II Div 2
    Hazardous Locations per NEC Art. 501 and 502. These cables also conform to Art. 392 "Cable Trays" and Art. 336 "Power and Control Tray Cable: Type TC."