    首頁 > > An-INDUSTRIAL TRAY CABLE (TC)

    PVC-Nylon/PVC PVC-nylon insulation PVC Jacket  90°C, 600 V Industrial Tray Cable PVC尼龍絕緣+PVC被覆工業控制電纜 (UL TC-ER)
    看原圖
    5639127

    商品編號: A-2A-1802

    PVC-Nylon/PVC PVC-nylon insulation PVC Jacket 90°C, 600 V Industrial Tray Cable PVC尼龍絕緣+PVC被覆工業控制電纜 (UL TC-ER)

    Designed for power and control, telemetering, relay control, traffic control, switching, lighting and signal transmission. May be used in Class I, Div. 2 and Class II, Div. 2
    Hazardous Locations per NEC Art. 501 and 502. These cables also conform to Art. 392 "Cable Trays" and Art 336 "Power and Control Tray Cable."

    Industrial Tray Cable

    PVC-Nylon/PVC

    PVC-nylon insulation
    PVC jacket
    90°C, 600 V


    SPECIFICATIONS
    1. CONDUCTORS:
    Class B stranded bare copper per UL 83 and 62
    2. INSULATION:Polyvinyl Chloride (PVC) per UL 62 for Type TFFN (18-16 AWG) or UL 83 for Type THWN or THHN wire, nominal thickness is 15 mils for sizes 18-12 AWG and 20 mils
    for 10 AWG
    3. INSULATION JACKET: Each insulated conductor is jacketed with nylon meeting UL 62 for Type TFFN or UL 83 for Type THWN or THHN wire, minimum thickness is 4 mils
    4. COLOR CODE: ICEA Method 1, Table E-2 (formerly K-2)
    5. ASSEMBLY:Conductors are cabled with fillers where necessary to make round, two conductor cables are flat
    6. OVERALL JACKET: Sunlight-resistant Polyvinyl Chloride (PVC) per UL 1277
    7. STANDARDS: Meets UL 1277 requirements for Type TC cables having THWN or THHN (TFFN) conductors, cables are listed for direct burial and meet the IEEE 1202, IEEE 383 and
    UL 1685 Btu/hr flame tests. Three conductor and larger constructions meet UL 1277 requirements for Exposed Runs and are rated Type TC-ER (Tray Cable, Exposed Runs)
    8. AMPACITY: Based on not more than three conductors in raceway or cable or earth with an ambient temperature of 30ºC per NEC Table 310.16, the values have been derated
    where applicable
    9. TEMPERATURE:90ºC
    10.VOLTAGE: 600 V
     

    APPLICATIONS
    Designed for power and control, telemetering, relay control, traffic control, switching, lighting and signal transmission. May be used in Class I, Div. 2 and Class II, Div. 2
    Hazardous Locations per NEC Art. 501 and 502. These cables also conform to Art. 392 "Cable Trays" and Art 336 "Power and Control Tray Cable."