PART NUMBER:71502
DESCRIPTION:14/2 STRANDED CMP/CL3P/FPLP FT6 PLENUM CABLE
CONSTRUCTION:This cable consists of two bare copper insulated conductors and an overall jacket.
APPROVALS:UL Standard 13, 444 & 1424; NEC Articles 725, 760 & 800.
APPLICATION:Communications Cable, Class 3 Power Limited Circuit Cable and/or Fire Alarm Power Limited Circuit Cable used for Plenum Applications
.
Construction Parameters:
Conductor 14 AWG Bare Copper
Stranding 19/.0147"
Insulation Material Low Smoke PVC
Insulation Thickness 0.008 Nom.
Insulated Conductor Diameter 0.086 Nom.
Number of Conductors 2
Lay Length 5.00 Nom.
Jacket Material Low Smoke PVC
Jacket Thickness 0.017 Nom.
Overall Cable Diameter 0.206 Nom.
Approximate Cable Weight 38.0 Lbs/1M Nom.
Flame Rating NFPA 262 Steiner Tunnel Smoke and Flame Test
Electrical Properties:
Temperature Rating -20OC to 75OC
Operating Voltage 300V Max per NEC Article 725
Capacitance Between Conductors @ 1 KHz 43 pF/ft Nom.
Capacitance Between Conductors to Shield @ 1 KHz -----
DC Resistance per Conductor @ 20OC 2.52 Ohms/1M Nom.
Insulation Colors Black Red
Jacket Color Beige