PART NUMBER:75306
DESCRIPTION:22/6 STRANDED SHIELDED CL3P/CMP/FPLP FT6 PLENUM CABLE
CONSTRUCTION:This cable consists of six bare copper insulated conductors, cabled with an overall shield
and drain wire, and an overall jacket.
APPROVALS:UL Standard 13 and 444, NEC Articles 725, 800, and 760.
APPLICATION:Power Limited Circuit Cable And Communications Cable Used in Plenum Applications
Construction Parameters:
Conductor 22 AWG Bare Copper
Stranding 7/30
Insulation Material Low Smoke PVC
Insulation Thickness 0.010 Nom.
Insulated Conductor Diameter 0.049 Nom.
Number of Conductors 6
Lay Length 4.00 Nom.
Shield Alum/Mylar
Drain 24 AWG 7/32 Tinned Copper
Jacket Material Low Smoke PVC
Jacket Thickness 0.017 Nom.
Overall Cable Diameter 0.191 Nom.
Approximate Cable Weight 27.4 Lbs/1M Nom.
Flame Rating NFPA 262 Steiner Tunnel Smoke and Flame Test
Electrical Properties:
Temperature Rating -20OC to 75C
Operating Voltage 300 V RMS Max.
Capacitance Between Conductors @ 1 KHz 39 pF/ft Nom.
Capacitance Between Conductors to Shield @ 1 KHz 73 pF/ft Nom.
DC Resistance per Conductor @ 20OC 16.19 Ohms/1M Nom.
Insulation Colors Black Red White Green Brown Blue
Jacket Color Beige (Other colors available for minimum order