1. CALEDONIAN-Fire Resistant Coaxial Cables 耐火級低煙無毒同軸電纜線
    CALEDONIAN-Fire Resistant Fire Alarm Cables (950°C 180 minutes)耐火級低煙無毒火警警報電纜線
    Caledonian-Fire Resistant Instrumentation Cables (950°C 180 minutes) 耐火級低煙無毒儀表控制電纜線
    CALEDONIAN-Fire Resistant Optic Fiber Cables 耐火級低煙無毒光纖電纜線
    Caledonian-Fire Resistant Power & Control Cables (950°C 180 minutes) 耐火級低煙無毒電力控制電纜線
    MICC/TRM/TET-Mineral Insulated Heating Units & Cable
    回上一頁
  2. 產品搜尋
    分 類:
    關鍵字:  

    首頁 > > CALEDONIAN-Fire Resistant Optic Fiber Cables 耐火級低煙無毒光纖電纜線

    CALEDONIAN-Fire resistant Central Loose Tube Fiber Optic cables 鬆式多芯單套管雲母帶耐火級低煙無毒(鎧裝)光纖電纜線
    看原圖
    5544253




    商品編號: CALEDONIAN-CLA-B-C-H-J-FR

    CALEDONIAN-Fire resistant Central Loose Tube Fiber Optic cables 鬆式多芯單套管雲母帶耐火級低煙無毒(鎧裝)光纖電纜線


    Application
    These cables are characterized by light weight and small diameter, suitable for both aerial and duct installation. They are mainly installed inside buildings, tunnels,subways or closed areas in general, specially designed to guarantee the signal transmission even in case of fire. The cable can also be used for direct burial for armoured version.
    Standards
    Basic design to Telcordia GR-20 / RUS 7 CFR 1755.900 (REA PE-90) / ICEA S 87-640
     




    ★★★★商品說明★★★★

    PRODUCTS

    Fire Resistant Optic Fiber Cables
    Fire resistant Central Loose Tube Fiber Optic cables
    Application
    These cables are characterized by light weight and small diameter, suitable for both aerial and duct installation. They are mainly installed inside buildings, tunnels,subways or closed areas in general, specially designed to guarantee the signal transmission even in case of fire. The cable can also be used for direct burial for armoured version.
    Standards
    Basic design to Telcordia GR-20 / RUS 7 CFR 1755.900 (REA PE-90) / ICEA S 87-640
    FIRE PERFORMANCE

    Circuit Integrity

    IEC 60331-25; BS 6387 CWZ; DIN VDE 0472-814(FE180);

    CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);

    NF C32-070-2.3(CR1)

    System circuit integrity

    DIN 4102-12, E30 depending on lay system

    Flame Retardance (Single Vertical Wire Test)

    EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

    CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

    Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

    EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

    Halogen Free

    IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

    CEI 20-37/2-1 ; BS 6425-1*

    No Corrosive Gas Emission

    IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

    CEI 20-37/2-2 ; BS 6425-2*

    Minimum Smoke Emission

    IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

    CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

    No Toxic gases

    NES 02-713; NF C 20-454

    Note: Asterisk * denotes superseded standard.
    CABLE CONSTRUCTION
    Fibers: Singlemode and multimode fibers, with loose tube technology.
    Structure: Central loose tube cable contains one tube with 2-24 single or multimode fibers, which are filled with water blocking gel.
    Fire barrier: The jelly filled tube with up to 24 fibers is wrapped with a fire blocking mica glass tapes.
    Water blocking: The jelly filled tube is waterblocked by using swellable tape and thread.
    Reinforcement: Either aramid yarn or fiber glass is wound around the tube to provide physical protection and tensile strength, with added fire protection.
    Inner sheath (optional): The cable can be jacketed with either PE or thermoplastic LSZH inner sheath. PE is the preferred option in outdoor environment for water protection purpose.
    Moisture Barrier Tape (optional): An aluminum moisture tape can be incorporated under the sheath for water blocking and shielding purpose.
    Armouring(optional):
    For diect burial, either galvanized steel wire braid, corrugated steel tape armour or galvanized steel wire armour is applied over an inner polyethylene or LSZH sheath. For steel tape armour, the 0.15mm thick steel tape is coated with a copolymer and applied with an overlap. For steel wire braid or armour, single layer of galvanized steel wire braid or armour is applied.
    Ripcord (optional): An optional ripcord can be located under the jacket to facilitate jacket removal.
    Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1(Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)


     



    ★★★★使用操作說明★★★★

    TYPE CODES

     

    CLA-B-C-D-E-F-G-FR

    FR: Fire Resisting

    Water blocking gel in tubes

     

    X: No water-blocking J: Water blocking gel between jackets; D: Dry water-blocking between cable jackets

    Outer Sheath

    2Y: PE

    Y: PVC

    H: LSZH

    Armour

    Blank: No armour

    STA: Corrugated steel tape armour

    SWA: Steel wire armour

    SWB: Steel wire braid

    Inner Sheath

    2Y: PE

    Y: PVC

    H: LSZH

     

    C No of FibersB Fiber Type

    4:50/125 um(OM3) 7: NZDS SM fiber per ITU-T G.656

    5:50/125 um(OM2) 8: NZDS SM fiber per ITU-T G.655

    6:62.5/125um(OM1) 9: Standard SM fiber per ITU-T G.652.D

     

    Tube Diameter

    A: 2.7mm

    B: 3.5mm

    C: 4.2mm