PRODUCTSFire Resistant Coaxial Cables Fire resistant RG6 A/U Coaxial cables RG6 A/U FR APPLICATION The cables are designed for CCTV, security, smoke detection and evacuation monitoring applications, where continued functionality is required during a fire situation. Due to the zero halogen low smoke construction, this cable is ideal for use in public, commercial and industrial environments. Standards Basic design to MIL-C-17 FIRE PERFORMANCE Circuit Integrity | IEC 60331-23; BS 6387 CWZ; DIN VDE 0472-814(FE180); CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) | System circuit integrity | DIN 4102-12, E30 depending on lay system | Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* | Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 | Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* | No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* | Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* | No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard. CABLE CONSTRUCTION Conductors: Bare copper copper wire, solid according to IEC(EN) 60228 class 1. Insulation: Foamed PE wrapped with fire resistant silicone rubber compound type EI2 as per BS 7655-1.1 or fluoropolymer(FEP) compound. Binder: Glass tape Overall Screen: AL foil(100%)+AL braid (70%) Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.) Physical AND THERMAL PROPERTIES Temperature range during operation (fixed state): -30°C - +70°C Temperature range during installation (mobile state): -5ºC - +60ºC Minimum bending radius: 8 x Overall Diameter Electrical Properties Impedance | 75±5Ω | Capacitance | 54 nF/km | Velocity ratio(%) | 82 | Insulation resistance | >5000 Mohm.Km | Shield coverage | AL foil(100%)+AL 70% | DC resistance | | Inner conductor | 23.1 Ω/km | Outer conductor | 31 Ω/km |
Attenuation Frequency(MHz) | Attenuation (dB/100 m) | Attenuation (dB/100ft) | 50 | 5.0 | 1.5 | 100 | 6.4 | 1.96 | 200 | 9.2 | 2.8 | 500 | 14.5 | 4.4 | 600 | 15.9 | 4.9 | 800 | 17.7 | 5.4 | 1000 | 21.9 | 6.7 | 1350 | 24.9 | 7.6 | 1750 | 29.0 | 8.8 | 2050 | 33.1 | 10.1 | 2400 | 36.4 | 11.1 |
Return Loss Frequency(MHz) | Return Loss (dB) | 30-300 | >28dB | 300-600 | >24dB | 600-900 | >22dB |

|