1. CALEDONIAN-Fire Resistant Coaxial Cables 耐火級低煙無毒同軸電纜線
    CALEDONIAN-Fire Resistant Fire Alarm Cables (950°C 180 minutes)耐火級低煙無毒火警警報電纜線
    Caledonian-Fire Resistant Instrumentation Cables (950°C 180 minutes) 耐火級低煙無毒儀表控制電纜線
    CALEDONIAN-Fire Resistant Optic Fiber Cables 耐火級低煙無毒光纖電纜線
    Caledonian-Fire Resistant Power & Control Cables (950°C 180 minutes) 耐火級低煙無毒電力控制電纜線
    MICC/TRM/TET-Mineral Insulated Heating Units & Cable
    回上一頁
  2. 產品搜尋
    分 類:
    關鍵字:  

    首頁 > > CALEDONIAN-Fire Resistant Fire Alarm Cables (950°C 180 minutes)耐火級低煙無毒火警警報電纜線

    CALEDONIAN-JE-H(St)H Fire Resistant 300V Mica+LSZH Insulated & LSZH Sheathed Fire Alarm Cables (950°C 180 minutes) 多對型雲母帶耐火級低煙無毒鋁箔隔離火警警報電纜線
    看原圖
    5543606




    商品編號: CALEDONIAN-JE-Bd

    CALEDONIAN-JE-H(St)H Fire Resistant 300V Mica+LSZH Insulated & LSZH Sheathed Fire Alarm Cables (950°C 180 minutes) 多對型雲母帶耐火級低煙無毒鋁箔隔離火警警報電纜線


    APPLICATION
    The cables are used for the internal wiring of building when the circuit integrity during fire is
    paramount. The cables are intended for use in fire fighting plants with mica tapes, with and without
    Aluminum foil and LSZH outer sheath.The fire alarm cables with 30 to 90 minutes circuit integrity
    should be used for control voltages and data transfer in alarm and fire alarm systems, where a
    system circuit integrity E30/E60/E90 depending on lay system in accordance with DIN 4102-12 is
    required. The circuit integrity is guaranteed with a test voltage of 110V.
    STANDARDS
    Basic design to VDE 0815




    ★★★★商品說明★★★★

    PRODUCTS

    Fire Resistant Fire Alarm Cables
    300V Mica+LSZH Insulated & LSZH Sheathed Fire Alarm Cables
    FFX200P 05mROZ1-R (CU/MICA+XLPE/OSCR/LSZH 300/500V Class 2 )
    APPLICATION
    The cables are designed, manufactured and tested as data transmission cables for emergency services. These are primarily intended for for indoor instrumentation and control cabling, electrically noisy environments and fire alarm systems in office buildings when high frequency signal transmission has to be assured in the event of a fire.
    STANDARDS
    Basic design to BS 7629-1
    FIRE PERFORMANCE

    Circuit Integrity

    IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);

    CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);

    NF C32-070-2.3(CR1)

    System circuit integrity

    DIN 4102-12, E30 depending on lay system

    Flame Retardance (Single Vertical Wire Test)

    EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;

    VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

    CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

    Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

    EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

    Halogen Free

    IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

    CEI 20-37/2-1 ; BS 6425-1*

    No Corrosive Gas Emission

    IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

    CEI 20-37/2-2 ; BS 6425-2*

    Minimum Smoke Emission

    IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

    CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

    No Toxic gases

    NES 02-713; NF C 20-454

    Note: Asterisk * denotes superseded standard.
    CABLE CONSTRUCTION
    Conductors: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
    Insulation: Mica glass tape covered by extruded cross-linked XLPE compound or cross-linked compound type EI5 as per BS 7655: section 5.1.
    Cabling Elements: Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two-pair cable had four cores laid in quad formation.
    Cabling: Pairs are cabled together. In cables with 8 pairs or more, 4 pairs are assembled to form a bunch, the bunches are then cabled together.
    Overall screen: Aluminum/polyester tape with tinned copper drain wire.
    Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
    COLOUR CODE
    Insulation Colour: According to IEC 60189-2 (other colour code on request).
    Sheath Colour: Colour red (other colours on request).
    Physical AND THERMAL PROPERTIES
    Temperature range during operation (fixed state): -30°C - +90°C
    Temperature range during installation (mobile state): -20°C - +50°C
    Minimum bending radius: 8 x Overall Diameter