    CALEDONIAN-FFX300 Fire Resistant 600/1000V Mica+XLPE Insulated, LSZH Sheathed Power Cables (Single-Core) 雲母耐火級XLPE + 低煙無毒電纜線(可鎧裝)
    看原圖
    5542868




    商品編號: CALEDONIAN-FFX300-1000

    CALEDONIAN-FFX300 Fire Resistant 600/1000V Mica+XLPE Insulated, LSZH Sheathed Power Cables (Single-Core) 雲母耐火級XLPE + 低煙無毒電纜線(可鎧裝)


    This cable is designed for areas where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, communications systems, sewage treatment plants, lifts, escalators, and high-rise buildings.
    STANDARDS
    Basic design to IEC 60502-1 / BS 6724
     




    ★★★★商品說明★★★★

    PRODUCTS

    Fire Resistant Power & Control Cables
    600/1000V Mica+XLPE Insulated, LSZH Sheathed Power Cables (Single-Core)
    FFX300 1mRZ1-R (CU/MGT+XLPE/LSZH 600/1000V Class 2)
    FFX300 1mRMZ1-R (CU/MGT+XLPE/LSZH/AWA/LSZH 600/1000V Class 2)
    APPLICATION
    This cable is designed for areas where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, communications systems, sewage treatment plants, lifts, escalators, and high-rise buildings.
    STANDARDS
    Basic design to IEC 60502-1 / BS 6724
    FIRE PERFORMANCE

    Circuit Integrity

    IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);

    CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)

    System circuit integrity

    DIN 4102-12, E30 depending on lay system

    Flame Retardance (Single Vertical Wire Test)

    EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;

    VDE 0482-332-1 ; NBN C 30-004 (cat. F1);

    NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*;

    DIN VDE 0482-265-2-1*

    Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

    EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

    Halogen Free

    IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

    CEI 20-37/2-1 ; BS 6425-1*

    No Corrosive Gas Emission

    IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

    CEI 20-37/2-2 ; BS 6425-2*

    Minimum Smoke Emission

    IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

    CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

    No Toxic gases

    NES 02-713; NF C 20-454

    Note: Asterisk * denotes superseded standard.
    VOLTAGE RATING
    600/1000 V
    CABLE CONSTRUCTION
    Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
    Insulation: Mica glass tape covered by extruded cross-linked XLPE compound
    Inner Sheath (optional):Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1
    Armouring (optional): Aluminum wire armour
    Outer Sheath:Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
    COLOUR CODE
    Insulation Colour: Natural (other colors upon request)
    Sheath Colour: Orange (other colors upon request)
    Physical AND THERMAL PROPERTIES
    Temperature range during operation (fixed state): -30°C – +90°C
    Temperature range during installation (mobile state): -20°C – +50°C
    Minimum bending radius: 8 x Overall Diameter (unarmoured cable)
    10 x Overall Diameter (armoured cable)
    Electrical PROPERTIES

    Dielectric test:

    3500 V r.m.s. x 5’ (core/core)

    Insulation resistance

    1000 MΩ x km (at 20°C)

    Short circuit temperature

    250°C