1. CALEDONIAN-Fire Resistant Coaxial Cables 耐火級低煙無毒同軸電纜線
    CALEDONIAN-Fire Resistant Fire Alarm Cables (950°C 180 minutes)耐火級低煙無毒火警警報電纜線
    Caledonian-Fire Resistant Instrumentation Cables (950°C 180 minutes) 耐火級低煙無毒儀表控制電纜線
    CALEDONIAN-Fire Resistant Optic Fiber Cables 耐火級低煙無毒光纖電纜線
    Caledonian-Fire Resistant Power & Control Cables (950°C 180 minutes) 耐火級低煙無毒電力控制電纜線
    MICC/TRM/TET-Mineral Insulated Heating Units & Cable
    回上一頁
  2. 產品搜尋
    分 類:
    關鍵字:  

    首頁 > > Caledonian-Fire Resistant Power & Control Cables (950°C 180 minutes) 耐火級低煙無毒電力控制電纜線

    CALEDONIAN-FFX200 Fire Resistant 300/500V Mica+XLPE Insulated, LSZH Sheathed Power Cables (2-4cores) 雲母耐火級XLPE + 低煙無毒控制電纜
    看原圖
    5542879




    商品編號: CALEDONIAN-FFX200

    CALEDONIAN-FFX200 Fire Resistant 300/500V Mica+XLPE Insulated, LSZH Sheathed Power Cables (2-4cores) 雲母耐火級XLPE + 低煙無毒控制電纜


    APPLICATION
    The cables are designed for areas where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, lifts, escalators, and high-rise buildings.
    STANDARDS
    Basic design to IEC 60502-1
     




    ★★★★商品說明★★★★

    PRODUCTS

    Fire Resistant Power & Control Cables
    300/500V Mica+XLPE Insulated, LSZH Sheathed Power Cables (2-4cores)
    FFX200 05mRZ1-R ( CU/MGT+XLPE/LSZH 300/500V Class 2)
    APPLICATION
    The cables are designed for areas where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, lifts, escalators, and high-rise buildings.
    STANDARDS
    Basic design to IEC 60502-1
    FIRE PERFORMANCE

    Circuit Integrity

    IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);

    CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3);

    NF C32-070-2.3(CR1)

    System circuit integrity

    DIN 4102-12, E30 depending on lay system

    Flame Retardance (Single Vertical Wire Test)

    EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;

    VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

    CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

    Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

    EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

    Halogen Free

    IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

    CEI 20-37/2-1 ; BS 6425-1*

    No Corrosive Gas Emission

    IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

    CEI 20-37/2-2 ; BS 6425-2*

    Minimum Smoke Emission

    IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

    CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

    No Toxic gases

    NES 02-713; NF C 20-454

    Note: Asterisk * denotes superseded standard.
    VOLTAGE RATING
    300/500 V
    CABLE CONSTRUCTION
    Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
    Insulation: Mica glass tape covered by extruded cross-linked XLPE compound
    Earth Conductor(optional): Uninsulated solid or stranded tinned copper conductor.
    Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
    Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
    COLOUR CODE
    Insulation Colour
    2 - Core: (Brown & Blue)
    3 - Core: (Brown, Black & Grey)
    4 - Core: (Brown, Black, Grey & Blue)
    Sheath Colour
    Orange (other colors upon request)
    Physical AND THERMAL PROPERTIES
    Temperature range during operation (fixed state): -30°C – +90°C
    Temperature range during installation (mobile state): -20°C – +50°C
    Minimum bending radius: 8 x Overall Diameter
    Electrical PROPERTIES

    Dielectric test:

    2000 V r.m.s. x 5’ (core/core)

    Insulation resistance

    1000 MΩ x km (at 20°C)

    Short circuit temperature

    250°C