    首頁 > > Caledonian-Fire Resistant Power & Control Cables (950°C 180 minutes) 耐火級低煙無毒電力控制電纜線

    CALEDONIAN-FFX200E Fire Resistant 300/500V Mica+SR Insulated & Overall Screened Control Cables (2-4 Cores & Multicores) 雲母耐火級矽橡膠 + 低煙無毒鋁箔隔離控制電纜
    看原圖
    5542955




    商品編號: CALEDONIAN-FFX200E

    CALEDONIAN-FFX200E Fire Resistant 300/500V Mica+SR Insulated & Overall Screened Control Cables (2-4 Cores & Multicores) 雲母耐火級矽橡膠 + 低煙無毒鋁箔隔離控制電纜


    APPLICATION
    The cables are primarly intended for use in the following applications:
    BS 5266-1 for emergency lighting of premises
    BS 5839-1 for fire detection and fire alarm systems in and around building
    BS 5839-8 for voice alarm systems
    BS 5839-9 for emergency voice communication systems.
    STANDARDS
    Basic design to BS 7629-1
     




    ★★★★商品說明★★★★

    PRODUCTS

    Fire Resistant Power & Control Cables
    300/500V Mica+SR Insulated & Overall Screened Control Cables (2-4 Cores & Multicores)
    FFX200E 05mSOZ1-U (PH120) (CU/MGT+SR/OSCR/LSZH 300/500V Class 1)
    FFX200E 05mSOZ1-R (PH120) (CU/MGT+SR/OSCR/LSZH 300/500V Class 2)
    APPLICATION
    The cables are primarly intended for use in the following applications:
    BS 5266-1 for emergency lighting of premises
    BS 5839-1 for fire detection and fire alarm systems in and around building
    BS 5839-8 for voice alarm systems
    BS 5839-9 for emergency voice communication systems.
    STANDARDS
    Basic design to BS 7629-1
    FIRE PERFORMANCE

    Circuit Integrity

    IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);

    BS 8434-2 (120mins); BS 5839-1 Clause 26 2e; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)

    Circuit Integrity with mechanical shock

    EN 50200(PH120); CEI 20-36/4-0

    Circuit Integrity with mechanical shock & water spray

    EN 50200 annex E

    System circuit integrity

    DIN 4102-12, E30 depending on lay system

    Flame Retardance (Single Vertical Wire Test)

    EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;

    VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);

    CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

    Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

    EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

    Halogen Free

    IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;

    CEI 20-37/2-1 ; BS 6425-1*

    No Corrosive Gas Emission

    IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;

    CEI 20-37/2-2 ; BS 6425-2*

    Minimum Smoke Emission

    IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;

    CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

    No Toxic gases

    NES 02-713; NF C 20-454

    Note: Asterisk * denotes superseded standard.
    VOLTAGE RATING
    300/500 V
    CABLE CONSTRUCTION
    Conductors: Plain annealed copper wire, solid according to IEC(EN) 60228 class 1, stranded according to IEC(EN) 60228 class 2.
    Insulation: Mica glass fire resistant tape covered by fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.
    Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
    Overall screen: Aluminum/polyester tape with tinned copper drain wire.
    Circuit Protective Conductor: Uninsulated tinned copper conductor of the same section and class as the insulated conductors in the 2-, 3- and 4-core cables. Drain wire of 0.5mm2 tinned copper conductor is provided in cables of more than 4 conductors.
    Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
    COLOUR CODE
    Insulation Colour
    2 cores blue - brown
    3 cores brown - black - grey
    4 cores blue - brown - black - grey
    (Colour Code Up To 4 Cores In Accordance to HD 308)
    7 cores centre: brown 1st layer: brown - black - 4 cores white
    12 cores centre: brown - black - white 1st layer: brown - black - 7 cores white
    19 cores centre: brown 1st layer: brown - black - 4 cores white
    2nd layer: brown - black - 10 cores white
    (on request the cores can be one colour only, identified by printed numbers
    Sheath Colour: Colour red or white (other colours on request)
    Physical AND THERMAL PROPERTIES
    Temperature range during operation (fixed state): -30°C – +90°C
    Temperature range during installation (mobile state): -20°C – +50°C
    Minimum bending radius: 7.5 x Overall Diameter
    Electrical PROPERTIES

    Dielectric test:

    2000 V r.m.s. x 5’ (core/core)

    Insulation resistance

    ≥300 MΩ x km (at 20°C)

    Short circuit temperature

    350°C