PRODUCTSFire Resistant Power & Control Cables 300/500V Mica+SR Insulated & Overall Screened Control Cables (2-4 Cores & Multicores) FFX200E 05mSOZ1-U (PH120) (CU/MGT+SR/OSCR/LSZH 300/500V Class 1) FFX200E 05mSOZ1-R (PH120) (CU/MGT+SR/OSCR/LSZH 300/500V Class 2) APPLICATION The cables are primarly intended for use in the following applications: BS 5266-1 for emergency lighting of premises BS 5839-1 for fire detection and fire alarm systems in and around building BS 5839-8 for voice alarm systems BS 5839-9 for emergency voice communication systems. STANDARDS Basic design to BS 7629-1 FIRE PERFORMANCE Circuit Integrity | IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-2 (120mins); BS 5839-1 Clause 26 2e; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) | Circuit Integrity with mechanical shock | EN 50200(PH120); CEI 20-36/4-0 | Circuit Integrity with mechanical shock & water spray | EN 50200 annex E | System circuit integrity | DIN 4102-12, E30 depending on lay system | Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* | Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 | Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* | No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* | Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* | No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard. VOLTAGE RATING 300/500 V CABLE CONSTRUCTION Conductors: Plain annealed copper wire, solid according to IEC(EN) 60228 class 1, stranded according to IEC(EN) 60228 class 2. Insulation: Mica glass fire resistant tape covered by fire resistant silicone rubber compound type EI2 as per BS 7655-1.1. Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers. Overall screen: Aluminum/polyester tape with tinned copper drain wire. Circuit Protective Conductor: Uninsulated tinned copper conductor of the same section and class as the insulated conductors in the 2-, 3- and 4-core cables. Drain wire of 0.5mm2 tinned copper conductor is provided in cables of more than 4 conductors. Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.) COLOUR CODE Insulation Colour 2 cores blue - brown 3 cores brown - black - grey 4 cores blue - brown - black - grey (Colour Code Up To 4 Cores In Accordance to HD 308) 7 cores centre: brown 1st layer: brown - black - 4 cores white 12 cores centre: brown - black - white 1st layer: brown - black - 7 cores white 19 cores centre: brown 1st layer: brown - black - 4 cores white 2nd layer: brown - black - 10 cores white (on request the cores can be one colour only, identified by printed numbers Sheath Colour: Colour red or white (other colours on request) Physical AND THERMAL PROPERTIES Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 7.5 x Overall Diameter Electrical PROPERTIES Dielectric test: | 2000 V r.m.s. x 5’ (core/core) | Insulation resistance | ≥300 MΩ x km (at 20°C) | Short circuit temperature | 350°C |

|