    5L-1401  14-1C 19 STR TNC DLO TS CPE JKT 1KV 90C   1 kV Diesel-Locomotive Cable 柴油機車電纜
    看原圖
    5146848

    商品編號: A-5L-1401

    5L-1401 14-1C 19 STR TNC DLO TS CPE JKT 1KV 90C 1 kV Diesel-Locomotive Cable 
    柴油機車電纜


     
    Thermoset CPE jacket
    90°C, 1 kV

    Applications:


    Portable or fixed power cable for use in drilling rigs, diesel-electric locomotives, railroad and transit car wiring, where reliability is a prime concern. Also suitable for electrically-driven earth-moving equipment, water-heater leads, power and control jumpers, case wiring and motor leads.

    Specifications:
    1. CONDUCTOR: Extra flexible, tinned, annealed, stranded copper, a suitable separator is applied over the conductor
    2. INSULATION/JACKET: Thermoset CPE
    3. STANDARDS: Conforms to ICEA S-95-658 (NEMA WC70), approved by the U.S. Coast Guard and the American Bureau of Shipping for offshore drilling rig use, sizes 1/0 and larger meet the IEEE 383 flame test
    4. AMPACITY: Based on not more than three conductors in raceway or cable or earth per NEC Table 310.16, an ambient temperature of 30°C and a conductor temperature of 90°C. For single conductors in free air per NEC Table 310.17, see following page.
    5. TEMPERATURE: 90°C
    6. VOLTAGE: 1 kV

    Tech. Info & Standards:


    CONDUCTOR: Extra flexible, tinned, annealed, stranded copper. A suitable separator is applied over the conductor.
    OVERALL JACKET: Hypalon.
    STANDARDS: Conforms to ICEA S-95-658 (NEMA WC70). Approved by the U.S. Coast Guard and the American Bureau of Shipping for offshore drilling rig use. Sizes 4/0 and larger meet the IEEE 383 flame test.
    AMPACITY: Based on not more than three conductors in raceway or cable or earth per NEC Table 310.16. Based on an ambient temperature of 30 C and a conductor temperature of 90° C.
    TEMPERATURE: 90° C
    VOLTAGE: 1 kV

     
    Single conductor also available in Type W. UL and CSA also available. For similar cables that are UL Listed, see the 3BF and 5N part number series. Diameters and weights may vary among manufacturers.
     
    Anixter Part No. Conductor Size Circular Mils Approximate Size AWG/kcmil No. of Strands Insulation Thickness (in.) Nominal O.D. (in.) Approx. Wt. lb/1000 ft Amps per Conductor
     5L-1401   3,831   14   19   0.062   0.19   30   24
     5L-1201   6,088   12   19   0.062   0.21   39   29
    5L-1001   10,910   10   27   0.062   0.25   57   41
     5L-0801   14,950   8   37   0.078   0.30   83   51
    5L-0601   24,640   6   61   0.078   0.34   124   71
      5L-0401   42,420   4   105   0.078   0.40   108   95
     5L-0201   60,600   2   150   0.078   0.48   254   121
     5L-0101   90,900   1   225   0.094   0.58   381   156
    5L-1011   111,100   1/0   275   0.094   0.65   527   175
    5L-2021   131,300   2/0   325   0.094   0.69   569   193
    5L-3031   181,800   3/0   450   0.094   0.78   844   236
      5L-4041   222,200   4/0   550   0.094   0.82   888   268
    5L-2621   262,600   262.6   650   0.109   0.88   1,006   297
      5L-3131   313,100   313.1   775   0.109   0.96   1,197   327
      5L-3731   373,700   373.7   925   0.109   1.01   1,396   364
     5L-4441   444,400   444.4   1100   0.109   1.10   1,652   402
     5L-5351   535,300   535.3   1325   0.125   1.23   2,003   445
      5L-6461   646,600   646.6   1600   0.125   1.32   2357   496
      5L-7771   777,700   777.7   1925   0.125   1.38   2806   546