M2XH-FFR
HALOGEN-FREE, FLAME RETARDANT, FIRE RESISTANT POWER CABLE
CABLE STRUCTURE
1- CONDUCTOR : Electrolytic, stranded, annealed copper wire IEC 60228 Class 2 (Class 5 and/or tinned on request).
2- SEPERATOR : Mica tape.
3- INSULATION : Halogen-free, crosslinked polyethylene compound (XLPE).
4- SEPERATOR : Separating foil or halogen-free bedding compound on request.
5- OUTER SHEATH : Halogen-free, flame retardant and fire resistant, thermoplastic polyolefin based compound (HM4 / SHF1) - HD 604 - IEC 332 / 3. Color: Green.
PRODUCTION AND TEST STANDARDS
CONSTRUCTION : IEC 60092/353
TESTS AND MATERIAL : IEC 60092 /350-351-359
FLAME RETARDATION : IEC 60332/1, IEC 60332/3
FIRE RESISTANCE : IEC 60331
HALOGEN CONTENT : IEC 60754 / 1 - 2
SMOKE DENSITY : IEC 61034 / 1-2 ( DIN EN 50268/1-2)
WORKING TEMPERATURE : -40°C / + 90°C
MIN. BENDING RADIUS (FIXED) : 6 x ( Overall Diameter)
RATED VOLTAGE : 0,6 / 1 kV T
TEST VOLTAGE : 3,5 kV
APPLICATION
Used on marine vehicles as fixed installation cables of various electromechanical and electronic equipments, where sustainable connection during fire is required.
ENVIRONMENT
Usable at all conditions in marine environment such as dry, wet or oily locations.
SAFETY
Even at direct contact with fire, it will sustain the connection for 180min. That provides necessary equipment (fire alarm and extinguishing systems, water pumps, communication, radio, control systems, lightning, etc.) to work uninterrupted during a fire. Due to its halogen-free, low smoke density and flame retardant features, it wont create corrosive gases nor obstruct visibility and prevents the fire from spreading around. Thus it protects human life and equipment, during a fire.