商品編號: JWEI-TUV-PV, google, msn,yahoo,
TUV Specification of Photovoltaic (PV) Power Cables 歐規太陽能光伏電纜
歐規 TÜV PV Cable
.鍍錫無氧銅,溫水式交連PE絕緣外被
.分為600V/1000V雙層絕緣
.導體規格 2.5mm2、3.5mm2、4.0mm2、6.0mm2
.顏色可訂做黑、紅、藍色
.額定電壓600V/1000V,額定溫度-40℃ ~ 90℃
.抗紫外線,耐水,耐油,耐鹽,耐臭氣,阻燃,低煙無鹵
.遵照RoHS標準
.TÜV安規認證:
|
歐規TUV Specification of Photovoltaic Power Cables
|
European Standard TUV Double Layer U0/U 0.6/1KV
|
Item
|
|
PVD-625T
|
PVD-640T
|
PVD-660T
|
TUV
|
mm2
|
2.50
|
4.00
|
6.00
|
Section Size
|
AWG
|
13
|
11
|
9
|
Structure
|
|
50/0.254 TC
|
80/0.254TC
|
85/0.30 TC
|
Conductor ID
|
mm
|
2.1
|
2.6
|
3.2
|
Thickness
|
mm
|
0.70
|
0.70
|
0.80
|
XLPE Insulation ID
|
mm
|
3.5
|
4.0
|
4.8
|
Thickness
|
mm
|
0.90
|
0.95
|
1.05
|
XLPE Jacket OD
|
mm
|
5.3
|
5.9
|
6.9
|
OD Tolerance
|
mm
|
±0.2
|
±0.2
|
±0.2
|
Bending Radius
|
mm
|
> 4 x CABLE OUTER DIAMETER
|
Weight
|
kg / 100M
|
5.39
|
7.51
|
10.36
|
Allow Current
|
A / mm2
|
31.2
|
41.2
|
51.8
|
Conductor Resistance R20 max
|
Ω/km
|
8.21
|
5.09
|
3.39
|
Application
Double insulated, moisture curable cross-linked cables for Photovoltaic power applications.
Construction
Conductor: Tinned copper strands, according to VDE 0295 / IEC 60228, class 5 / UL854 class B
Insulation: Polyolefin Copolymer moisture curable cross-linked
Outer sheath: Polyolefin Copolymer moisture curable cross-linked
Sheath color: Black, Red, Blue, All Color
Technical specification
voltage rating: U0/U 0.6/1KV
Test voltage: 3000 V, 60 Hz, 1 min.
Temperature rating: 90 °C dry or wet
194 °F dry or wet
Ambient temperature: > 25 years (TÜV)
– 40 °C up to + 90 °C
– 40 °F up to + 194 °F
Max. short circuit temperature: 250 °C, +482 °F
Bending radius: ≥ 4 × outer diameter |
|
Marking
TÜV JINWEI PVD***UT PV1-F 1X***mm2 20##
Standards / Material properties
Approvals: TUV
Application standards: 2Pfg 1169 / 08.2007
Features & Benefits
Robust design.
Moisture curable cross-linked.
Resistance against UV, water, ozone, fluids, oil, salt and general weathering.
Flame retardant.
Three colors: Red, Blue and Black.
RoHS compliant.
TUV certified.
Compatible to all popular connectors
|
歐規TUV Specification of Photovoltaic Power Cables
|
European Standard TUV Double Layer U0/U 0.6/1KV
|
Item
|
PV1-F
|
PVD-625T
|
PVD-640T
|
PVD-660T
|
TUV
|
mm2
|
2.50
|
4.00
|
6.00
|
Section Size
|
AWG
|
13
|
11
|
9
|
Structure
|
|
50/0.254 TC
|
80/0.254TC
|
85/0.30 TC
|
Conductor ID
|
mm
|
2.1
|
2.6
|
3.2
|
Thickness
|
mm
|
0.70
|
0.70
|
0.80
|
XLPE Insulation ID
|
mm
|
3.5
|
4.0
|
4.8
|
Thickness
|
mm
|
0.90
|
0.95
|
1.05
|
XLPE Jacket OD
|
mm
|
5.3
|
5.9
|
6.9
|
OD Tolerance
|
mm
|
±0.2
|
±0.2
|
±0.2
|
Bending Radius
|
mm
|
> 4 x CABLE OUTER DIAMETER
|
Weight
|
kg / 100M
|
5.39
|
7.51
|
10.36
|
Allow Current
|
A / mm2
|
31.2
|
41.2
|
51.8
|
Conductor Resistance R20 max
|
Ω/km
|
8.21
|
5.09
|
3.39
|
|
|