Type-name
GI-30AC type
SI-30AC type
ZI-30AC type
Application
For the station buildings with
steel tower, which are located
in the Nipponkai coast and have high probability of direct lightning strikes with extreamly high lightning energy especially in winter this type is the most suitable equipment and uses the lightning protector which has the biggest current capacity in the world corresponding to JIS.
For the station with steel tower,
where direct lightning strikes are predicted a lot of this standard type equipment have been installed actually. This type is the most suitable type for micro-wave relay station on the mountain top and for the measures to lightning strikes in summer.
For the protection of equipment installed in the downtown of the big cities, where the direct lightning strike is very seldom and the measures to the inductive lightning from low voltage distribution line are mainly necessary, this type is the most suitable equipment with excellent cost performance.
Rated in-and output voltage
according to customer’s designation
Number of phase
Single phase 2W, Single phase 3W, 3 phase 3W
Rated frequency
50or60(Hz)
Transformer capacity
according to customer’s designation
Protection level
less than 200(V)
Withstanding to impulse voltage
(between primary and secondary, between primary and grounding)
1.2/50μs 30kV
Withstanding to commercial voltage
(between primary and secondary, between primary and grounding)
AC10kV in 1 minute
Withstanding to impulse current
10/350μs 50kA
4/10μs 100kA
8/20μs 20kA
Circuit diagram
(Example ; Single phase side shows 2W)