8718
 |
|
Multi-Conductor - Single-Pair Cable
12 AWG stranded (19x25) TC conductors, polyethylene insulation, twisted pair, overall Beldfoil® shield (100% coverage), 14 AWG stranded TC drain wire, PVC jacket. |
For more Information
please call
1-800-Belden1 |
Item # |
Putup |
Ship Weight |
Color |
Notes |
Item Desc |
8718 060U500 |
500 FT |
47.500 LB |
CHROME |
|
2 #12 PE SHLD PVC |
8718 0601000 |
1,000 FT |
100.000 LB |
CHROME |
C |
2 #12 PE SHLD PVC |
8718 0602000 |
2,000 FT |
198.000 LB |
CHROME |
C |
2 #12 PE SHLD PVC |
8718 060500 |
500 FT |
46.000 LB |
CHROME |
C |
2 #12 PE SHLD PVC |
|
Notes: |
|
C = CRATE REEL PUT-UP.
|
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs |
AWG |
Stranding |
Conductor Material |
1 |
12 |
19x25 |
TC - Tinned Copper |
|
Insulation
Insulation Material:
Insulation Material |
Wall Thickness (in.) |
PE - Polyethylene |
.037 |
|
Outer Shield
Outer Shield Material:
Outer Shield Trade Name |
Type |
Outer Shield Material |
Coverage (%) |
Beldfoil® (Z-Fold®) |
Tape |
Aluminum Foil-Polyester Tape |
100 |
|
Outer Shield Drain Wire AWG:
AWG |
Stranding |
Drain Wire Conductor Material |
14 |
Stranded |
TC - Tinned Copper |
|
Outer Jacket
Outer Jacket Material:
Outer Jacket Material |
Nom. Wall Thickness (in.) |
PVC - Polyvinyl Chloride |
.040 |
|
Overall Cabling
Overall Nominal Diameter: |
0.400 in. |
Pair
Pair Color Code Chart:
Number |
Color |
1 |
Black & Clear |
|
Pair Lay Length & Direction:
Lay Length (in.) |
Twists/ft. (twist/ft) |
2.000 |
6.000 |
|
Mechanical Characteristics (Overall)
Operating Temperature Range: |
-20°C To +80°C |
UL Temperature Rating: |
80°C (UL AWM Style 20253) |
Bulk Cable Weight: |
93 lbs/1000 ft. |
Max. Recommended Pulling Tension: |
225 lbs. |
Min. Bend Radius (Install)/Minor Axis: |
4 in. |
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: |
CL2 |
AWM Specification: |
UL Style 20253 (600 V 80°C) |
EU Directive 2000/53/EC (ELV): |
Yes |
EU Directive 2002/95/EC (RoHS): |
Yes |
EU RoHS Compliance Date (mm/dd/yyyy): |
01/01/2004 |
EU Directive 2002/96/EC (WEEE): |
Yes |
EU Directive 2003/11/EC (BFR): |
Yes |
CA Prop 65 (CJ for Wire & Cable): |
Yes |
MII Order #39 (China RoHS): |
Yes |
Other Specification: |
C(UL) AWM II, A |
Flame Test
UL Flame Test: |
UL1685 UL Loading |
Plenum/Non-Plenum
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Nom. Inductance:
Nom. Capacitance Conductor to Conductor:
Nom. Capacitance Cond. to Other Conductor & Shield:
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft) |
1.6 |
|
Max. Operating Voltage - UL:
Voltage |
600 V RMS (UL AWM Style 20253); 300 V RMS (CSA) |
|
Max. Recommended Current:
Current |
12.5 Amps per conductor @ 25°C |
|