1. (太平洋/華新/華榮)電線電纜區
    600V-380度耐熱電線電纜-1
    600V-380度耐熱電線電纜-2
    600V-380度耐熱電線電纜-3
    600V-840度耐熱電線電纜-1C
    600V-840度耐熱電線電纜-3C
    600V-840度耐熱電線電纜-4C
    LSFH-XLPE低煙無毒電線
    回上一頁
  2. 產品搜尋
    分 類:
    關鍵字:  

    首頁 > > Belden-工業電腦(FOUNDATION Fieldbus or PROFIBUS Cable)用線

    Belden-1332A Type A, 18 AWG, 20 Pairs, PLTC ITC DataBus® ISA/SP-50 FOUNDATION Fieldbus or PROFIBUS Cable
    看原圖
    5337057




    商品編號: Belden-1332A

    Belden-1332A Type A, 18 AWG, 20 Pairs, PLTC ITC DataBus® ISA/SP-50 FOUNDATION Fieldbus or PROFIBUS Cable


    Multi-Conductor - DataBus® ISA/SP-50 FOUNDATION Fieldbus or PROFIBUS Cable
    20 pair, 18 AWG stranded (7x26) tinned copper conductors, polyolefin insulation, individual & overall Beldfoil® shield (100% coverage), tinned copper drain wire, oil-resistant PVC jacket.




    ★★★★商品說明★★★★

    1332A
       Multi-Conductor - DataBus® ISA/SP-50 FOUNDATION Fieldbus or PROFIBUS Cable
    20 pair, 18 AWG stranded (7x26) tinned copper conductors, polyolefin insulation, individual & overall Beldfoil® shield (100% coverage), tinned copper drain wire, oil-resistant PVC jacket.
     
    Put Ups and Colors:
    Item # Putup Ship Weight Color Notes Item Desc
    1332A 0031000 1,000 FT 589.000 LB ORANGE C 20 FS PR #18 PP FS FRPVC
    1332A 0031640 1,640 FT 936.440 LB ORANGE C 20 FS PR #18 PP FS FRPVC
    1332A 0061000 1,000 FT 589.000 LB BLUE, LIGHT C 20 FS PR #18 PP FS FRPVC
    1332A 0061640 1,640 FT 936.440 LB BLUE, LIGHT C 20 FS PR #18 PP FS FRPVC
    Notes:  
    C = CRATE REEL PUT-UP.
     
    Physical Characteristics (Overall)
    Conductor
    AWG:
    # Pairs AWG Stranding Conductor Material Dia. (in.)
    20 18 7x26 TC - Tinned Copper .048
    Insulation
    Insulation Material:
    Insulation Material
    PO - Polyolefin
    Inner Shield
    Inner Shield Material:
    Inner Shield Trade Name Type Inner Shield Material Coverage (%)
    Beldfoil® Tape Aluminum Foil-Polyester Tape 100
    Inner Shield Drain Wire AWG:
    AWG Stranding Conductor Material
    20 7x28 TC - Tinned Copper
    Outer Shield
    Outer Shield Material:
    Outer Shield Trade Name Type Outer Shield Material Coverage (%)
    Beldfoil® Tape Aluminum Foil-Polyester Tape 100
    Outer Shield Drain Wire AWG:
    AWG Stranding Drain Wire Conductor Material
    18 7x26 TC - Tinned Copper
    Outer Jacket
    Outer Jacket Material:
    Outer Jacket Material
    PVC - Polyvinyl Chloride
    Outer Jacket Ripcord: Yes
    Overall Cabling
    Overall Nominal Diameter: 1.020 in.
    Pair
    Pair Color Code Chart:
    Number Color
    1 Blue & Orange Numbered 1
    2 Blue & Orange Numbered 2
    3 Blue & Orange Numbered 3
    4 Blue & Orange Numbered 4
    5 Blue & Orange Numbered 5
    6 Blue & Orange Numbered 6
    7 Blue & Orange Numbered 7
    8 Blue & Orange Numbered 8
    9 Blue & Orange Numbered 9
    10 Blue & Orange Numbered 10
    11 Blue & Orange Numbered 11
    12 Blue & Orange Numbered 12
    13 Blue & Orange Numbered 13
    14 Blue & Orange Numbered 14
    15 Blue & Orange Numbered 15
    16 Blue & Orange Numbered 16
    17 Blue & Orange Numbered 17
    18 Blue & Orange Numbered 18
    19 Blue & Orange Numbered 19
    20 Blue & Orange Numbered 20
    Pair Lay Length & Direction:
    Lay Length (in.) Twists/ft. (twist/ft)
    2.000 6.000
    Mechanical Characteristics (Overall)
    Operating Temperature Range: -30°C To +90°C
    UL Temperature Rating: 90°C
    Max. Recommended Pulling Tension: 1148 lbs.
    Min. Bend Radius (Install)/Minor Axis: 10.200 in.
    Applicable Specifications and Agency Compliance (Overall)
    Applicable Standards & Environmental Programs
    CEC/C(UL) Specification: CMG
    EU CE Mark: Yes
    EU Directive 2000/53/EC (ELV): Yes
    EU Directive 2002/95/EC (RoHS): Yes
    EU RoHS Compliance Date (mm/dd/yyyy): 09/01/2006
    EU Directive 2002/96/EC (WEEE): Yes
    EU Directive 2003/11/EC (BFR): Yes
    CA Prop 65 (CJ for Wire & Cable): Yes
    MII Order #39 (China RoHS): Yes
    Flame Test
    UL Flame Test: UL1685 FT4 Loading
    IEC Flame Test: 60332-3-24 (Category C)
    IEEE Flame Test: 1202
    Suitability
    Suitability - Indoor: Yes
    Suitability - Outdoor: Yes
    Sunlight Resistance: Yes
    Oil Resistance: Yes
    Plenum/Non-Plenum
    Plenum (Y/N): No
    Electrical Characteristics (Overall)
    Unaveraged Impedance:
    Description Freq. (MHz) Start Freq. (MHz) Stop Freq. (MHz) Impedance (Ohm)
      .03125     100
    Nom. Inductance:
    Inductance (µH/ft)
    .19
    Nom. Capacitance Conductor to Shield:
    Capacitance (pF/ft)
    45.0
    Nom. Mutual Capacitance:
    Capacitance (pF/ft)
    24.0
    Maximum Capacitance Unbalance:
    Capacitance (pF/ft)
    1.2
    Nominal Velocity of Propagation:
    VP (%)
    66
    Nom. Conductor DC Resistance:
    DCR @ 20°C (Ohm/1000 ft)
    5.86
    Nominal Outer Shield DC Resistance:
    DCR @ 20°C (Ohm/1000 ft)
    4.9
    Ind. Pair Nominal Shield DC Resistance @ 20 Deg. C: 7.500 Ohm/1000 ft
    Nom. Attenuation:
    Description Freq. (MHz) Start Freq. (MHz) Stop Freq. (MHz) Attenuation (dB/100 ft.)
      .039     .08
    Max. Attenuation:
    () Freq. (MHz) Attenuation (dB/100 ft.)
    .091 0.039 0.091
    Max. Operating Voltage - UL:
    Voltage
    300 V RMS
    Max. Recommended Current:
    Description Current
    Per Conductor 5.2 Amps
    Other Electrical Characteristic 1: Max Propagation Delay Change From 7.812 kHz to 39.06 kHz: 518 pS/ft
    Other Electrical Characteristic 2: 31.25 KBits/sec