For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet or dry locations. For direct earth burial.
XLP insulation Inner and outer PVC jackets Aluminum interlocked armor
SPECIFICATIONS 1. CONDUCTOR:Class B stranded, bare, soft copper, for single conductor cables the minimum size is AWG #6 2. INSULATION: Cross-Linked Polyethylene (XLP) Type RW-90 per CSA C22.2, No. 131 3. GROUNDING CONDUCTOR: Composed of individual wires applied helically over the insulation 4. INNER JACKET: Polyvinyl Chloride (PVC) 5. ARMOR: Aluminum interlocking armor (for single conductor cables for use in AC circuits aluminum armor only is provided and non-magnetic [aluminum] connectors and locknuts must be used) 6. OUTER JACKET:Polyvinyl Chloride (PVC) heat-, flame- and moisture-resistant jacket, rated -40°C, the standard color is black but colored jackets will be provided on request 7. STANDARDS: The cable is certified to CSA C22.2 No. 131 Type Teck 90 and No. 174 for use in CSA Class 1, Division 1, hazardous locations (CSA HL rated) and passes the FT4 vertical tray flame test 8. AMPACITY: Based on 90°C column of Table 1 of the 2009 Canadian Electric Code, allowable ampacities for single copper conductors in free air based on 30°C ambient temperature 9. TEMPERATURE: -40°C to 90°C 10.VOLTAGE:1 kV
APPLICATIONS For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet or dry locations. For direct earth burial.