    首頁 > > An-Armor Cable Teck 90 & Accessories 金屬鎧裝電纜

    A- TECK 90 (CSA) XLP/Galv. Steel or Aluminum Armor/Jackets 1kV 2芯耐高壓波紋鋁管or波紋鋼管鎧裝電力控制電纜
    看原圖
    5260313




    商品編號: A-7TJ-1402

    A- TECK 90 (CSA) XLP/Galv. Steel or Aluminum Armor/Jackets 1kV 2芯耐高壓波紋鋁管or波紋鋼管鎧裝電力控制電纜


    For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet or dry
    locations. For direct earth burial.




    ★★★★商品說明★★★★

    Armored Cable
    Teck 90 (CSA)

    1 kV Two Conductor

    Galvanized steel or interlocked aluminum armor
    XLP insulation
    Inner and outer PVC jackets


    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, bare, soft copper
    2. INSULATION: Cross-Linked Polyethylene (XLP)
    3. COLOR CODING: Surface color coding is standard for sizes up to and including AWG #6, for larger than sizes number coding is standard
    4. GROUNDING CONDUCTOR: An uninsulated Class B stranded grounding conductor is included in the cable assembly
    5. ASSEMBLY: Multiple conductor cables are assembled with suitable fillers and binder tape
    6. INNER JACKET: Polyvinyl Chloride (PVC)
    7. ARMOR: Aluminum or galvanized steel interlocking armor
    8. OUTER JACKET: Polyvinyl Chloride (PVC) heat-, flame- and moisture-resistant jacket, rated -40°C, the standard color is black but colored jackets are available on request
    9. STANDARDS: The cable is certified to CSA C22.2 No. 131 for Type Teck 90 and No. 174 for use in CSA Class 1, Division 1 hazardous locations (CSA HL rated). Cable passes
    IEEE 1202/FT4 vertical tray flame test
    10.AMPACITY: Based on 90°C column of Table 2 of the 2009 Canadian Electric Code, allowable ampacities for not more than 3 copper conductors in raceway or cable based on
    30°C ambient temperature
    11.TEMPERATURE: -40°C to 90°C
    12.VOLTAGE:1 kV
     

    APPLICATIONS
    For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet or dry
    locations. For direct earth burial.