Armored Cable
Norteck (UL and CSA)
600 V Three Conductor
Aluminum interlocked armor
XLP insulation
Inner and outer PVC jackets
UL 600 V, CSA 1 kV
SPECIFICATIONS
1. CONDUCTOR:Class B stranded, bare, annealed copper per ASTM B3 and B8
2. INSULATION: Cross-Linked Polyethylene (XLP) per ICEA S-95-658 (NEMA WC70), Type RHH/RHW-2 requirements of UL 44 and RW90 requirements of CSA. Color coding is
Method 1, Table E-2
3. ASSEMBLY: The insulated conductors are cabled with a single uninsulated ground wire and fillers to make round
4. INNER JACKET:Black, sunlight-resistant Polyvinyl Chloride (PVC). Jacket meets low acid gas requirements of CSA C22.2 No. 0.3
5. ARMOR: Aluminum-interlocked
6. OVERALL JACKET:Black, sunlight-resistant polyvinyl chloride (PVC) applied overall per ICEA, jacket meets low acid gas requirements of CSA C22.2 No. 0.3
7. STANDARDS: Cables meet UL 1685 and IEEE1202/FT4 (70,000 Btu/hr) and ICEA T-29-520 (210,000 Btu/hr) flame tests, and are marked "for CT use". Cables also meet
CSA -40°C cold impact and bend test. Individual conductors UL Listed Type RHH/RHW-2 per UL 44 and listed CSA Type RW90. Completed cables listed Type MC per UL 1569 and
CSA Type Teck 90 per CSA C22.2 No. 131
8. AMPACITY: Based on not more than three conductors in raceway or cable or earth based on an ambient temperature of 30°C per 2008 NEC table 310.16
9. TEMPERATURE:90°C
APPLICATIONS
For use in power circuits in industrial plants, commercial buildings, and central and substation utility applications. May be installed in trays, racks, hangers, etc.,
eliminating the need for conduit. Suitable for indoor and outdoor installation. May be used in Class I and II, Div 2 locations.