    A-EPR/Aluminum interlocked armor/PVC 5KV 105°C Three Conductor Nonshielded Armored Cable  EPR/PVC 3芯耐高壓波浪狀鋁管鎧裝控制電纜
    看原圖
    5258966




    商品編號: A-7BB-0603A

    A-EPR/Aluminum interlocked armor/PVC 5KV 105°C Three Conductor Nonshielded Armored Cable EPR/PVC 3芯耐高壓波浪狀鋁管鎧裝控制電纜


    For use in power circuits in industrial plants, commercial buildings, and central and substation utility applications. May be installed in trays, racks, hangers, etc.,
    eliminating the need for conduit. Suitable for indoor and outdoor installation.




    ★★★★商品說明★★★★

    Armored Cable
    Interlocked Armor

    5 kV Three Conductor Shielded

    Aluminum interlocked armor
    EPR insulation
    133% insulation level


    SPECIFICATIONS
    1. CONDUCTOR:
    Class B stranded, bare, annealed copper per ASTM B3, strand shield is an extruded
    semiconducting material
    2. INSULATION: Ethylene Propylene Rubber (EPR) per ICEA S-93-639 (NEMA WC74)
    3. SHIELDING: An extruded semiconducting thermosetting insulation shield is applied over the insulation, an uncoated copper tape is helically applied overall per ICEA S-93-639
    4. ASSEMBLY:The three-phase conductors are cabled with a Class B stranded, uninsulated ground wire and fillers to make round, a binder tape is applied overall
    5. ARMOR: Aluminum interlocked armor
    6. OVERALL JACKET: Extruded, yellow Polyvinyl Chloride (PVC) that meets UL sunlight-resistance requirements
    7. STANDARDS: Listed Type MV-105 per UL 1072 and Type MC per UL 1569 and meets ICEA S-93-639 requirements. Cable passes the UL 1685 and IEEE 1202 (70,000 Btu/hr) and
    ICEA T-29-520 (210,000 Btu/hr) flame tests and are listed "for CT use"
    8. AMPACITY:Based on a three-conductor cable isolated in air with a conductor temperature of 105°C and an ambient temperature of 40°C per 2008 NEC table 310.71
    9. TEMPERATURE: 105°C
    10.VOLTAGE: 5 kV


    APPLICATIONS
    For use in power circuits in industrial plants, commercial buildings, and central and substation utility applications. May be installed in trays, racks, hangers, etc.,
    eliminating the need for conduit. Suitable for indoor and outdoor installation.