    首頁 > > An-INDUSTRIAL TRAY CABLE (TC)

    FREP/CPE EPR Insulation CPE Jacket  90°C, 600 V Industrial Tray Cable EPR絕緣+CPE被覆工業控制電纜 (UL TC)
    看原圖
    5257181

    商品編號: A-2MR-1402

    FREP/CPE EPR Insulation CPE Jacket 90°C, 600 V Industrial Tray Cable EPR絕緣+CPE被覆工業控制電纜 (UL TC)


    Designed for power and control, telemetering,relay control, traffic control, switching, lightingand signal transmission. May be used inClass 1, Div. 2 Hazardous Locations perNEC Art. 501. These cables also conformto Art. 318 “Cable Trays” and Art. 340“Power and Control Tray Cable.”

    EPR Insulation
    CPE Jacket
    90°C, 600 Volts

    APPLICATIONS:
    Designed for power and control, telemetering,
    relay control, traffic control, switching, lighting
    and signal transmission. May be used in
    Class 1, Div. 2 Hazardous Locations per
    NEC Art. 501. These cables also conform
    to Art. 318 “Cable Trays” and Art. 340
    “Power and Control Tray Cable.”

    SPECIFICATIONS:
    1. CONDUCTORS:
    Class B stranded tinned copper per ASTM B-3, B-8 and B-33.
    2. INSULATION: Ethylene propylene rubber (EPR) per ICEA S-73-532 (NEMA WC57).
    Meets UL 44 requirements for VW-1, Type XHHW-2 conductors.
    3. COLOR CODE: Conductors shall be color coded per ICEA Method 1, Table E-2 (formerly K-2).
    4. ASSEMBLY: Conductors are cabled with fillers where necessary to make round. Two
    conductor cables are flat.
    5. OVERALL JACKET: Sunlight resistant chlorinated polyethylene (CPE) per UL 1277.
    6. STANDARDS: Tested per UL requirements for Type TC cables having VW-1, XHHW-2
    conductors. Cables are listed for direct burial and meet the IEEE 1202, UL 1277 and
    ICEA 210,000 BTU flame tests.
    7. AMPACITY: Based on not more than three conductors in raceway or cable or earth with an
    ambient temperature of 30°C per NEC 310-16. The values have been derated where applicable.
    8. TEMPERATURE: 90°C
    9. VOLTAGE: 600 Volts