CCI-81402 Fire Alarm 14/2 SOLID BC FPLP Cables – Unshielded – Plenum Type FPLP Awg14x 2C 低煙型火災警報訊號傳輸線
|
81402 - 14/2 SOLID BC FPLP
|
|
 |
Fire Alarm Multi-Conductor Cables – Unshielded – Plenum Type FPLP
Features:
- Low Smoke PVC jacket
- Temperature rating 75°C
- High speed dispensing system (pullout boxes)
Applications:
- Power limited fire alarm and communications cable for plenum applications.
- Fire alarm, smoke detectors, signaling, fire protective circuits.
Industry Approvals:
- UL Type FPLP
- NEC Article 760
- cUL Type CMP/FT6
- California State Fire Marshall
|
PART NUMBER: 81402
DESCRIPTION: 14/2 SOLID FPLP FT6 CABLE
CONSTRUCTION: This cable consists of two bare copper insulated conductors and an overall jacket.
APPROVALS: UL Standard 1424, NEC Article 760.
APPLICATION: Fire Alarm Power Limited Circuit Cable Used in Plenum Applications
Construction Parameters:
Conductor 14 AWG Bare Copper
Stranding Solid
Insulation Material Low Smoke PVC
Insulation Thickness 0.008 Nom.
Insulated Conductor Diameter 0.080 Nom.
Number of Conductors 2
Lay Length 5.00" Nom.
Jacket Material Low Smoke PVC
Jacket Thickness 0.017 Nom.
Overall Cable Diameter 0.194 Nom.
Approximate Cable Weight 36.2 Lbs/1M Nom.
Flame Rating NFPA 262 Steiner Tunnel Smoke and Flame Test
Electrical Properties:
Temperature Rating -20度to 75度
Operating Voltage 300V RMS Max
Capacitance Between Conductors@1KHz 44Pf/ft Nom.
Capacitance Between Conductors to shield@1KHz ----
DC Resistance per Conductor@20度 2.54 Ohms/1M*Nom.
Insulation Colors Black Red Green Yellow
Jacket Colors Red (other colors available for min order)
Legend (Surface Ink Print) COLEMAN CABLE 81402 14 AWG 2/C C(ETL)US
-TYPE FPLP 75C
Testing Requirement: Spark Testing (Jacket and Insulation): 2KVAC (100% of manufactured cable)
Hypot Testing: 2.5KVDC (1 out of 10 reels)
Continuity: 100% (every packaged reel)
keyword: CCI 81402, UL1424, NEC Article 760,PLTC Fire Alarm Cable ,低煙無鹵型火災警報鋁箔總隔離訊號傳輸電纜線, , 長庚醫院, 故宮博物館, 火車捷運站, 南港展覽館, 演藝廳,音樂會場,google, anixter,圖書館, 百貨公司 |